Electrical Connections; 115- -V Wiring; J- -Box Relocation - Payne PG80ESAA Installation, Start-Up, Operating And Service And Maintenance Instructions

Single--stage, 4--way multipoise 33--1/3 in. non--condensing gas furnace input capacities 45,000 thru 155,000 btuh
Table of Contents

Advertisement

Volts-
Hertz-
Unit Size
Phase
36045A
115--- 60--- 1
36045B
115--- 60--- 1
36070A
115--- 60--- 1
36070B
115--- 60--- 1
48070C
115--- 60--- 1
42090B
115--- 60--- 1
48090C
115--- 60--- 1
60090C
115--- 60--- 1
60090D
115--- 60--- 1
60110C
115--- 60--- 1
60110D
115--- 60--- 1
60135D
115--- 60--- 1
60155D
115--- 60--- 1
* Permissible limits of the voltage range at which the unit operates satisfactorily.
# Unit ampacity = 125 percent of largest operating component's full load amps plus 100 percent of all other potential operating components' (EAC, humidifier,
etc.) full load amps.
{ Time ---delay type is recommended.
} Length shown is as measured one way along wire path between unit and service panel for maximum 2 percent voltage drop.

ELECTRICAL CONNECTIONS

!
WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow safety warnings could result in dangerous
operation, serious injury, death or property damage.
Improper servicing could result in dangerous operation,
serious injury, death or property damage.
- - Before servicing, disconnect all electrical power to
furnace.
- - When servicing controls, label all wires prior to
disconnection. Reconnect wires correctly.
- - Verify proper operation after servicing.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Blower access panel door switch opens 115- -v power to
control. No component operation can occur. Do not bypass
or close switch with panel removed.
See Fig. 25 for field wiring diagram showing typical field 115- -v
wiring. Check all factory and field electrical connections for
tightness.
Field- -supplied wiring shall conform with the limitations of 63_F
(35_C) rise.
WARNING
!
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal
injury, death, or property damage.
The cabinet MUST have an uninterrupted or unbroken
ground according to current edition of NEC NFPA 70 or
local codes to minimize personal injury if an electrical fault
should occur. This may consist of electrical wire, conduit
approved for electrical ground or a listed, grounded power
cord (where permitted by local code) when installed in
accordance with existing electrical codes. Refer to the
power cord manufacturer's ratings for proper wire gauge.
Do not use gas piping as an electrical ground.
Table 7 – Electrical Data
Operating Voltage*
Range
Ampacity#
Maximum
Minimum
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
Unit
Minimum Wire
Size AWG
7.8
14
10.3
14
7.8
14
7.8
14
13.3
14
11
14
11
14
16.9
12
13.5
14
17.4
12
14
14
14
14
14
14
!
FURNACE MAY NOT OPERATE
Failure to follow this caution may result in intermittent
furnace operation.
Furnace control must be grounded for proper operation or
else control will lock out. Control must remain grounded
through green/yellow wire routed to gas valve and manifold
bracket screw.

115- -V WIRING

Verify that the voltage, frequency, and phase correspond to that
specified on unit rating plate. Also, check to be sure that service
provided by utility is sufficient to handle load imposed by this
equipment. Refer to rating plate or Table 7 for equipment
electrical specifications.
Make all electrical connections in accordance with current edition
of National Electrical Code (NEC) NFPA 70 and any local codes
or ordinances that might apply.
!
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death, or property damage.
Do not connect aluminum wire between disconnect switch
and furnace. Use only copper wire.
Use a separate, fused branch electrical circuit with a properly
sized fuse or circuit breaker for this furnace. See Table 7 for wire
size and fuse specifications. A readily accessible means of
electrical disconnect must be located within sight of the furnace.
NOTE: Proper polarity must be maintained for 115- -v wiring. If
polarity is incorrect, control LED status indicator light will flash
rapidly and furnace will NOT operate.

J- -BOX RELOCATION

NOTE: If factory location of J- -Box is acceptable, go to next
section (ELECTRICAL CONNECTION TO J- -BOX).
NOTE: On 14- -in. (356 mm) wide casing models, the J- -Box
shall not be relocated to other side of furnace casing when the
vent pipe is routed within the casing.
1. Remove and save two screws holding J- -Box.
19
Maximum Wire
Length
feet
m
47
14.3
36
11
47
14.3
47
14.3
27
8.2
33
10.1
33
10.1
34
10.4
27
8.2
33
10.1
26
7.9
26
7.9
26
7.9
CAUTION
WARNING
Maximum
Fuse
or CKT
BKR Amps
15
15
15
15
15
15
15
20
15
20
15
15
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pg80esla

Table of Contents