Introduction R32, R290 air conditioner installation
1) Introduction to Refrigerants R32 & R290
The refrigerants used for air conditioners are environmentally friendly hydrocarbons R32 and R290. The two
kinds of refrigerants are combustible and odorless. Moreover, they can burn and explode under certain
condition. However, there will be no risk of burning and explosion if you comply with the following table to
install your air conditioner in a room with an appropriate area and use it correctly.
Compared with ordinary refrigerants, Refrigerants R32 & R290 are environmentally friendly and do not
destroy the ozone sphere and that their values of greenhouse effect are also very low.
2) R32/R290 air conditioner installation area requirement
3
m1=(4m
)×LFL, m2=(26m
Where LFL is the lower flammable limit in kg/m
For the appliances with a charge amount m1<M<m2:
The maximum charge in a room shall be in accordance with the flowing: M
The required minimum floor area A
accordance with following: A
Where:
M
is the allowable maximum charge in a room, in kg;
max
M is the refrigerant charge amount in appliance, in kg;
A
is the required minimum room area, in m2;
min
A is the room area, in m2;
LFL is the lower flammable limit, in kg/m3;
h0 is the installation height of the appliance, in meters for calculating M
LFL
Category
(kg/m3)
R290
0.038
R32
0.306
LFL
Category
(kg/m3)
R290
0.038
R32
0.306
Air Conditioner Service Manual
3
) ×LFL, m3=(130m
to install an appliance with refrigerant charge M(kg) shall be in
min
= (M/ (2.5 x (LFL)
min
Table GG.1 - Maximum charge (kg)
h0
(m)
4
0.6
0.05
1
0.08
1.8
0.15
2.2
0.18
0.6
0.68
1
1.14
1.51
1.8
2.05
2.71
2.2
2.5
3.31
Table GG.2 - Minimum room area (m2)
h0
(m)
0.152kg 0.228kg 0.304kg 0.456kg 0.608kg
0.6
/
82
1
/
30
1.8
/
9
2.2
/
6
1.224kg 1.836kg 2.448kg 3.672kg 4.896kg
0.6
/
29
1
/
10
1.8
/
3
2.2
/
2
3
) ×LFL
3
, R290 LFL is 0.038kg/m
(5/4)
0
x h
)) 2
Floor area (m
Maximum charge (kg)
7
10
15
0.07
0.08
0.1
0.11
0.03
0.06
0.2
0.24
0.29
0.24
0.29
0.36
0.9
1.08
1.32
1.8
2.2
3.24
3.97
3.96
4.85
Charge amount (M) (kg)
Minimum room area (m2)
146
328
53
118
16
36
11
24
51
116
19
42
6
13
4
9
3
, R32 LFL is 0.306kg/m
(5/4)
=2.5×(LFL)
×h
max
or A
, 1.8 m for wall mounted;
max
min
2
)
20
30
0.11
0.14
0.09
0.2
0.34
0.41
0.41
0.51
1.53
1.87
2.54
3.12
4.58
5.61
5.6
6.86
0.76kg
0.988kg
584
912
210
328
65
101
43
68
6.12kg
7.956kg
206
321
74
116
23
36
15
24
3
.
1/2
×A
0
50
0.18
0.3
0.53
0.65
2.41
4.02
7.254
8.85
1514
555
171
115
543
196
60
40
26