Mitsubishi Electric CMB-WP108NU-AA Service Handbook page 137

Table of Contents

Advertisement

[ VIII Troubleshooting ]
7110
1. Error Code
7110
Connection information signal transmission/reception error
2. Error definition and error detection method
The given indoor unit is inoperable because it is not properly connected to the outdoor unit in the same system.
3. Error source, cause, check method and remedy
Error source
Outdoor unit
(1)
Power to the transmission booster is cut off.
(2)
Power resetting of the transmission booster
and outdoor unit.
(3)
The model selection switch (SW5-7) on the
outdoor unit is set to OFF. (Normally set to
ON)
HWE2206A
Cause
- 126 -
Check method and remedy
1)
Confirm that the power to the transmission
booster is not cut off by the booster being
connected to the switch on the indoor unit.
(The unit will not function properly unless the
transmission booster is turned on.)
->Reset the power to the outdoor unit.
2)
Check the model selection switch on the out-
door unit (Dipswitch SW5-7 on the control
board.).
GB

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cmb-wp1016nu-aaCmb-wp108nu-abCmb-wp1016nu-ab