Nibe ClimateMaster Tranquility TC L Series Installation Operation & Maintenance page 13

Commmercial horizontal and vertical packaged water-source heat pump - 50hz
Table of Contents

Advertisement

ATIONS REQUIRE SERVICE ACCESS AREA
SCRIBED IN NOTES 5 AND 6.
RIGHT RETURN STRAIGHT DISCHARGE
CHARGE
BSP
BSP
A
Note 6
C
Figure 2: Horizontal Unit Pitch
D
E
LEGEND
P=Compressor Access Panel
P=Control Box Panel
ALL CONFIGURATIONS REQUIRE SERVICE ACCESS AREA
P=Blower Service Panel
P=Expansion Valve Access panel
Water Outlet 1-1/4" FPT (072-096) 1-1/2" FPT (120)
Water Inlet 1-1/4" FPT (072-096) 1-1/2" FPT (120)
Condensate 3/4" FPT
High Voltage 1-1/8" [2.9cm] KO
LEFT RETURN STRAIGHT DISCHARGE
ow Voltage 7/8" [2.2cm] KO
HANGER BRACKET DIMENSIONS
NTROL BOX
B
34.1"
PLAN VIEW
[86.6cm]
TOP
CAP
CONTROL BOX
V
V
O
CBP
CAP
M
P Q
R
FRONT
RIGHT RETURN RIGHT VIEW-
K
AIR COIL SIDE
RIGHT RETURN END DISCHARGE
ARGE
CAP
CAP
87"
FRONT
FRONT
[221cm]
1.0"
[2.54cm]
PLAN VIEW
TOP
CAP
4.3"
CBP
[10.8cm]
Air Coil - To obtain maximum performance, the air coil
should be cleaned before start-up. A 10% solution of
U
S
dishwasher detergent and water is recommended for
both sides of the coil. A thorough water rinse should
T
follow. UV based anti-bacterial systems may damage
1.3"
coated air coils.
[3.3cm]
LEFT RETURN LEFT VIEW-
ondensate
AIR COIL SIDE
LEFT RETURN END DISCHARGE
CBP
EAP
BSP
E
1
1
EAP
2
CAP
1/4" (6.4mm) pitch
2
CAP
toward drain for drainage
FRONT
DESCRIBED IN NOTES 5 AND 6.
SERVICE ACCESS
Note 6
3' (91 cm.)
RIGHT RETURN STRAIGHT DISCHARGE
Note 6
Drain Connection
BSP
BSP
A
Note 6
C
3
F
D
E
G
U
EAP
S
LEGEND
CAP=Compressor Access Panel
CBP=Control Box Panel
BSP=Blower Service Panel
EAP=Expansion Valve Access panel
1.3"
1=Water Outlet 1-1/4" FPT (072-096) 1-1/2" FPT (120)
[3.3cm]
2=Water Inlet 1-1/4" FPT (072-096) 1-1/2" FPT (120)
condensate drain
3=Condensate 3/4" FPT
4=High Voltage 1-1/8" [2.9cm] KO
5=Low Voltage 7/8" [2.2cm] KO
CAP
HANGER BRACKET DIMENSIONS
EAP
CONTROL BOX
34.1"
PLAN VIEW
[86.6cm]
BSP
CONTROL BOX
V
V
RIGHT RETURN RIGHT VIEW-
AIR COIL SIDE
RIGHT RETURN END DISCHARGE
CAP
CAP
FRONT
CAP
CBP
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility
Figure 3: Typical Horizontal Unit Installation
Figure 3: Typical Horizontal Unit Installation
Supply Air
CBP
5
4
Insulated supply duct with
at least one 90 deg elbow
Note 5, 6
to reduce air noise
NOTES:
All dimensions in table are inches (cm).
-
1. Service access is required for all removable panels and installer should take care to comply with all building codes and
allow adequate clearance for future field service.
2. Water inlet and water outlet connections are available on either side (left or right) of the unit. Qty (2x) MPT Plugs are
1
shipped loose in a plastic bag tied to the water leg in front of the unit. Installer must plug water inlet/outlet side not being
connected to.
EAP
3. Condensate drain is 3/4" FPT and is located on cabinet end opposite the compressor.
2
CAP
4. Electrical access is available on either side (left or right) of the front.
CAP
5. Electric box is on right side. It can be field converted to left side. Conversion should only be attempted by qualified
service technician. If electric box relocated to opposite side, and water connected to opposite side, then this access is
FRONT
not required.
6. Units require 3' (9.1 cm) clearance for water connections, CAP, CBP, EAP and BSP service access.
7. Overall cabinet width dimensions does not include filter rail and duct flange.
SERVICE ACCESS
Note 6
3' (91 cm.)
8. Units are shipped with air filter rails that are not suitable for supporting return air ductwork. An air filter frame with duct
mounting collar is available as an accessory.
Note 6
TOP
3
Notice! Installation Note - Ducted Return: Many
horizontal WSHPs are installed in a return air ceiling
S
U
plenum application (above ceiling). Vertical WSHPs are
commonly installed in a mechanical room with free return
(e.g. louvered door). Therefore, filter rails are the industry
standard and are included on ClimateMaster commercial
1.3"
[3.3cm]
heat pumps for the purposes of holding the filter only. For
condensate drain
ducted return applications, the filter rail must be removed
and replaced with a duct flange or filter frame. Canvas
CAP
FRONT
or flexible connectors should also be used to minimize
EAP
vibration between the unit and ductwork.
c l i m a t e m a s t e r. c o m
Compact Belt Drive ( TC _L) Series
®
Horizontal Installation (continued)
HORIZONTAL INSTALLATION
3/8" [10mm] threaded rods
(by others)
BSP
EAP
Flexible Duct
Connector
Stainless steel braid hose
with integral "J" swivel
Optional
Balancing Valve
Optional Low Pressure Drop Water
CBP
1
5
4
Note 5, 6
2
NOTES:
All dimensions in table are inches (cm).
-
1. Service access is required for all removable panels and installer should take care to com
allow adequate clearance for future field service.
2. Water inlet and water outlet connections are available on either side (left or right) of the
shipped loose in a plastic bag tied to the water leg in front of the unit. Installer must plug
connected to.
3. Condensate drain is 3/4" FPT and is located on cabinet end opposite the compressor.
4. Electrical access is available on either side (left or right) of the front.
5. Electric box is on right side. It can be field converted to left side. Conversion should onl
service technician. If electric box relocated to opposite side, and water connected to opp
not required.
6. Units require 3' (9.1 cm) clearance for water connections, CAP, CBP, EAP and BSP ser
7. Overall cabinet width dimensions does not include filter rail and duct flange.
8. Units are shipped with air filter rails that are not suitable for supporting return air ductwo
mounting collar is available as an accessory.
BSP
Rev.:24 Januar y, 2023
Return Air
CBP
Thermostat
Wiring
Unit
Power
CAP
CAP
Unit Hanger
Ball valve with optional
integral P/T plug
Building
Loop
Water In
Water Out
Control Valve
13