Toshiba MMU-UP0071YHP-UL Service Manual page 97

Table of Contents

Advertisement

<RBC-AWSU52-UL>
1
Push the [
MENU] button to display the menu
screen.
2
Push and hold the [
[
] button at the same time to display the
"Field setting menu".
• Push and hold the buttons for more than 4 seconds.
3
Push the [
] / [
"7. DN setting" on the "Field setting menu" screen,
then push the [
• When the group control is used, all the indoor units
connected into the system are displayed on the screen.
4
Push the to select indoor unit in which you want
to read out setting data in the EEPROM.
• The selected unit changes as follows each time the button
is pushed:
1-1
1-2
5
Push the" [
Set/Fix]" button.
• The setting display for the selected unit is displayed.
• The fan and louver of the indoor unit operate.
6
Push the [
] / [
[0001], then write down the setting data to be
displayed.
(Filter sign lighting time)
7
Repeat the operation of
setting data like Table 1. Setting data (CODE No. table
(example)).
∗ The Code No.(DN) are ranged in order of No., which may
be sometimes skipped.
8
After writing down all the setting data, push the
"[
Set/Fix
]"
S
• The setting display for the selected unit is displayed.
• When the group control is used, the fan and louver of the
selected indoor unit operate.
9
Push the [
MENU] button to set the other
"Code(DN)" and "Data". After "Continue?" is
displayed on the screen, push the [
b
utton to finish the setting operation. "
No
appears on the screen for a while, then the screen
returns to the "Field setting menu" screen.
MENU] button and the
] button to select
Set/Fix ] button.
] to set "DN code" to
1
6
to
, then write down the
Return ]
Setting"
- 97 -