Toshiba MMU-UP0071YHP-UL Service Manual page 20

Table of Contents

Advertisement

No.
Item
6
Fan speed
1) By the command from remote control, fan speed is
selection
2) When the fan speed mode [AUTO] is selected, the fan
• Fan speed mode [AUTO] in case when remote
controller sensor works is equal to that in case when
indoor unit sensor works.
• If the fan speed has been changed once, it is not
changed for 3 minutes. However when the air volume
is changed, the fan speed changes.
• When cooling operation has started, select a down-
ward slope for the fan speed, that is, the high position.
• If the temperature is just on the difference boundary,
the fan speed does not change .
(–0.9) –1.8
(+0.9) +1.8
(+1.8) +3.6
(+2.7) +5.4
(+3.6) +7.2
Value in the parentheses indicates one when sensor of
the remote controller works.
Value without parentheses indicates one when sensor
of the indoor unit sensor works.
• If the fan speed has been changed once, it is not
changed for 1 minute. However when the fan speed
changed, the fan speed changes.
• When heating operation has started, select an upward
slope for the fan speed, that is, the high position.
• If the temperature is just on the difference boundary,
the fan speed does not change.
• In TC2 ≥ 60˚C, the fan speed increases by 1 step.
Outline of specifications
changed. ((HH), (H+), (H), (L+), (L) or [AUTO])
speed varies by the difference between TA and Ts.
<COOL>
Ta ( °F)
Ta ( °C)
+3.0
+5.4
HH
+4.5
+2.5
<HH>
+3.6
+2.0
H+ <HH>
+2.7
+1.5
H <HH>
+1.8
+1.0
L+ <H+>
+0.9
+0.5
L <H>
Tsc
Tsc
L <H>
–0.9
–0.5
L <L+>
< > : Indicate automatic cooling.
Ta (°F)
Ta (°C)
L <L+>
(–0.5) –1.0
L+ <H>
(0) Tsh
(0) Tsh
H <H+>
(+0.5) +1.0
H+
<HH>
(+1.0) +2.0
HH
(+1.5) +3.0
<HH>
(+2.0) +4.0
< > : Indicate automatic heating.
Body thermostat works.
Remote controller thermostat works.
A
B
C
D
E
F
G
E
D
C
B
A
- 20 -
Remarks
HH > H+ > H > L+ > L > UL
Depending on the remote
controller used, (H+) and (L+)
cannot be selected.
For Floor Standing Concealed
Type,or Floor Standing Cabinet
Type, (HH), (H), (L) or [AUTO]
can be selected regardless of
remote controller models.
Code No. [32]
0000: Indoor unit sensor
(Main unit)
0001: Remote controller
sensor
TC2: Temperature of indoor
heat exchanger sensor