Power Connection

The FSR-424F-POE supports a redundant power option. Connect to separate
independent power sources for system redundancy.
Warning:
• This product is intended to be UL Listed supplied by a Power Adapter or
DC power source which output complies with provides double/reinforced
insulation from the AC mains: ambient temperature 75°C maximum, output
rating 18VDC to 40VDC, 6.5A Max and 41VDC to 125VDC, 15A Max
• If using Class I power adapter or Class I DC power source, power cord
shall be connected to a socket-outlet with earthing connection.
Caution:
The wiring of input terminal block shall be installed by skill person.
b. Terminal block is mating with plug and suitable for 14AWG minimum only,
wire type: Cu, FW2. Torque value 4.5 lb-in.
Separate
Power Outlet
or UPS
DC Power Supply
Note:
The GND pin of the terminal block (protective earthing terminal)
must be permanently connected to earth with a green with yellow stripe
conductor minimum size 14 AWG and the connection is to be installed by a
qualified service personnel
6
DC INPUT
18VDC-40VDC, 6.5A Max
41VDC-125VDC, 15A Max
V+
V-
GND
V+
V-
GND
GND
DC Power Supply
GND
Separate
Power Outlet
or UPS
7