The fan and power supply modules are field replaceable. You can replace one fan module or one power supply
module during operations so long as the other modules are installed and operating. If you have only one power
supply installed, you can install the replacement power supply in the open slot before removing the original
power supply.
Note
All fan and power supply modules must have the same direction of airflow. Otherwise, the switch can
overheat and shut down. If you are installing a dual-direction power supply, that module automatically
uses the same airflow direction as the other modules in the switch.
Caution
If the switch has port-side intake airflow (burgundy coloring for fan modules), you must locate the ports
in the cold aisle. If the switch has port-side exhaust airflow (blue coloring for fan modules), you must
locate the ports in the hot aisle. If you locate the air intake in a hot aisle, the switch can overheat and
shut down.
Cisco Nexus 9348D-GX2A ACI-Mode Switch Hardware Installation Guide