Specific conditions of use

WARNING
Always refer to the product certificates for any specific conditions of use.
Flameproof joints are not to be modified.
Cable temperature can exceed 60 °C. Use a suitable cable for the end application.
Cable entries into the equipment shall utilise suitably certified cable glands, thread
adaptors or plugs that shall provide a minimum degree of protection to maintain the
ingress rating of the equipment. As a minimum this should be IP66 or IP67.
Unused cable entry apertures shall be closed with suitably certified blanking plugs.
The protective guard on the thermal housings must not be removed.
Yield strength of the end cap fasteners is A4-80.
For coal mining applications, equipment shall only be installed where it has been
assessed that there is a low risk of mechanical damage from impacts which could
compromise the enclosure's flameproof protection.