LEGEND
1
Compressor
2
Condenser (BPHE)
3
Drier filter
4
Thermostatic expansion valve
5
Evaporator (BPHE)
6
Ball valve (optional)
7
Air purge valve (optional)
8
Water filter (optional)
9
Accumulator
10
Discharge stop valve
11
Sight glass
12
Liquid solenoid valve
13
Liquid stop valve
D-EIMHP01601-22_01EN 22/26

Figure 11- EWLQ 014 - 033 KCW1N Refrigerant circuit scheme

Figure 12- EWLQ 049 - 064 KCW1N Refrigerant circuit scheme

D1
Compressor-Condenser
L1-1
Condenser-Therm.Exp. Valve
L1-2
Therm.Exp Valve-Evaporator
S1
Evaporator-Compressor
S1-1
Evaporator-Accumulator
S1-2
Accumulator-Compressor
W1/W3
Water inlet assembly (Included kit,
but optional mounting)
W2/W4
Water outlet assembly (Included
kit, but optional mounting)
E1/E2
Equalizer pipe
TT
Temperature sensor
Pressure transducer (6,5 barg)
PT
PZH
High pressure switch (40,7
barg)
FS
Flow switch