4.7
Firing rates
The maximum output should be chosen within area A)(Fig. 2) of
the diagram.
The minimum output must not be lower than the minimum limit
of the diagram.
For model RLS 200/E MX
For operation within area B)(Fig. 2) advance the
shutter as shown in paragraph "Shutter move-
WARNING
ment" on page 24.
4.8
Test boiler
The firing rates were established in special test boilers, according
to EN 676 regulations.
In Fig. 3 you can see the diameter and length of the test combus-
tion chamber.
20121303
Technical description of the burner
Thermal power
10
GB
The firing rate was obtained with an ambient tem-
perature of 20°C and a barometric pressure of
1013 mbar (approx. 0m above sea level), with the
combustion head adjusted as shown on page 25.
WARNING
20101957
Example:
Output 756 kW (650 Mcal/h): diameter 60cm, length 2m.
Fig. 2
D715
Fig. 3