Refrigerant Line Set Installation - COMFORT-AIRE Century VMH09SU Series Installation And Operation Manual

Inverter single zone ductless mini-split
Table of Contents

Advertisement

Installation and Operation Manual - VMH 09/12/18/24 SU Series
VMH 09/12/18/24 SU/30 SD Inverter Mini-Split

Refrigerant Line Set Installation

Refrigerant Line Set Installation
1. Purchase line sets through a Heat Controller
distributor with consideration of the minimum and
maximum line lengths. (Fig, 20)
2. Ductless mini-splits require both-liquid and
suction-lines to be insulated.
3. Connections are made via flare nuts.
4. The number of bends and length of refrigerant
lines determine the pressure drop which affects
capacity and efficiency of the system, as well
as oil return. Minimize the length and number of
bends when possible during installation.
5. Minimum line set length must be maintained,
even if the installation does not require it. Extra
length that is unnecessary can be coiled up near
the outdoor unit (Do not to block air inlets/outlets).
6. Choose a location that places the outdoor unit as
close to the indoor unit as possible to minimize
line set lengths.
7. Use only clean, refrigerant grade tubing suitable
for R-410A.
8. Avoid installing refrigerant lines on wet/rainy
days.
9. Always keep tube ends sealed until the final
connections are to be made.
10.
If line sets are being made at the time of
installation, rather than being purchased, be sure
to:
• Remove burrs from cut ends of the tubing
• Use tube benders to prevent kinking.
• Ensure tube cuts are square in relation to the
end of the tube.
• Use the proper diameter tube and flare nut
sizes recommended by the manufacturer.
• Insulate both lines with Amaflex of equivalent
with a wall thickness of at least 3/8".
Liquid Side-Gas Side
Max. Refrigerant Pipe
Length Unit Separation*
Max. Level
Difference/Vertical Lift**
*Minimum pipe length must not be less that 10 feet.
** Trap rises every 10 feet (5-7m) with a 'p' trap when outdoor unit is mounted above
the indoor unit.
Refrigerant Piping
Inch
Ft.
(m)
Ft.
(m)
• Use copper tubing suitable to withstand
pressures for R-410A refrigerant. We
recommend a min. wall thickness of 0.027in.
(0.7mm).
11. The tube size should always be the same
diameter as the connections provided at the
service valves of the outdoor unit.
Note: On some models, a reducer or an expander
may be shipped with the indoor unit
in order to adapt the line set connection to
the proper size to mate with the indoor unit's
connection. Be sure to check for this part, should
you discover that the outdoor units service valve
sizes differ from the indoor unit. If this part is
shipped with the indoor unit, then it is required to
be used.
12. Up sizing/downsizing the refrigerant lines/
connections can result in inadequate oil return to
the compressor or excessive refrigerant return
and will void the warranty.
13. Do not over torque the connections, excessive
force can break the flare nut.
14. When routing the line set between the outdoor
and indoor units:
A. Support the tubing adequately to avoid sags
that can trap the oil.
B. Isolate the tubing so it does not transmit
noise from vibration into the structure of the
building.
C. Avoid sharp edges that could cut the tubes.
D. Trap rises every 10 ft. (5-7m) with a 'p' trap
when outdoor unit is mounted above
indoor unit.
Fig. 20
Model No.
VMH 09
VMH 12/18
1/4 - 3/8
1/4 - 1/2
82 (25)
82 (25)
98 (30)
33 (10)
33 (10)
66 (20)
10
10
Heat Controller
VMH 24
3/8 - 5/8
98 (30)
66 (20)

Advertisement

Table of Contents
loading

Table of Contents