esetting the time remaining to change the grid standard
The 24 hours are counted only when the inverter is turned on.
Check that the date and time are set correctly. Otherwise it may not be possible to access the
"Service" menu to reset the timer.
Settings
Service
The password to access the "Service" menu can be obtained by registering at the site https://
registration.abbsolarinverters.com
Before accessing the site it will be necessary to locate the information utilized to compute the
password:
Inverter model
Serial number and week of manufacture
Update field
The "Update" field is available only if the firmware of the inverter has been previously upda-
ted. If not available leave the field blank when requesting the password
The password obtained is valid for a period of 15 days
Reset Country S.
From the time a valid grid standard is entered and the inverter is turned
on, a period of 24 hours is available to modify the grid standard setting.
After this period of time the system will block changes to the standard;
and it will be necessary to carry out the following procedure to reset the
remaining time and obtain another 24 hours to select a new grid stan-
dard:
1. Access the "SETTINGS" menu by entering the first-level password
(default 0000)
2. Access the "Service" sub-menu by entering the second-level password
3. Select "Reset Country S." to reset the 24 hours of operation in which
the grid standard may be modified..