5.3 Configuration by computer

All settings can be changed by means of a computer.
Some settings can be changed with DIP switches (see Section 5.4).
For changing settings with the computer, the following is required:
- VEConfigure3 software: can be downloaded free of charge at www.victronenergy.com.
- A MK3-USB (VE.Bus to USB) interface, and a RJ45 UTP cable.
Alternatively, the Interface MK2.2b (VE.Bus to RS232) and a RJ45 UTP cable can be used.
5.4 Configuration with DIP switches
Some settings can be changed with DIP switches.
Procedure:
a) Turn the Multi on, preferably without load and without AC voltage on the input.
The Multi will then operate in inverter mode.
b) Set the DIP switches as required.
c) Store the settings by toggling DIP switch 3 one time.