ABB RELION 670 Series Commissioning Manual page 167

Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 511 366-UUS A
13.2.2
Using front-connected PC
When an internal fault has occurred, extensive information about the fault can be retrieved from
the list of internal events available in the SMS part:
TRM-STAT TermStatus - Internal Events
The list of internal events provides valuable information, which can be used during commissioning
and fault tracing.
The internal events are time tagged with a resolution of 1ms and stored in a list. The list can store
up to 40 events. The list is based on the FIFO principle, when it is full, the oldest event is
overwritten. The list cannot be cleared and its content cannot be erased.
The internal events in this list not only refer to faults in the IED, but also to other activities, such as
change of settings, clearing of disturbance reports, and loss of external time synchronization.
The information can only be retrieved from the Parameter Setting software package. The PC can
be connected either to the port at the front or at the rear of the IED.
These events are logged as internal events.
Table 17:
Event message:
INT--FAIL
INT--FAIL
INT--WARNING
INT--WARNING
IOn--Error
IOn--Error
ADMn-Error
ADMn-Error
MIM1-Error
MIM1-Error
INT--RTC
INT--RTC
INT--TSYNC
INT--TSYNC
INT--SETCHGD
DRPC-CLEARED
Commissioning manual
IED will not be operational during applications restart.
Events available for the internal event list in the IED
Description
Off
Internal fail status
Off
Internal warning status
Off
In/Out module No. n status
Off
Analog/Digital module No. n
status
Off
mA-input module status
Off
Real Time Clock (RTC) status
Off
External time synchronization
status
Any settings in IED changed
All disturbances in
Disturbance report cleared
Generating signal:
INT--FAIL (reset event)
INT--FAIL (set event)
lNT--WARNING (reset event)
lNT--WARNING (set event)
IOn--Error (reset event)
IOn--Error (set event)
ADMn-Error (reset event)
ADMn-Error (set event)
MIM1-Error (reset event)
MIM1-Error (set event)
INT--RTC (reset event)
INT--RTC (set event)
INT--TSYNC (reset event)
INT--TSYNC (set event)
Section 13
Troubleshooting
M11763-203 v4