Daikin ERLA11D V3 Series Installer's Reference Manual page 275

Hide thumbs Also See for ERLA11D V3 Series:
Table of Contents

Advertisement

ERLA11~16D + EBVH/X11+16S18+23D
Daikin Altherma 3 R F
4P643602-1B – 2022.05
#
Procedure
a
Display the current value.
Press BS3 once.
b
Change the value to 1.
Press BS2 once.
c
Enter the value in the system.
Press BS3 once.
d
Confirm.
Press BS3 once.
5
Return to the default situation.
Press BS1 once.
(a)
= OFF,
= ON, and
Result: The recovery mode is deactivated. The unit returns the electronic
expansion valves to their initial state.
INFORMATION
Power OFF. When power is turned OFF and turned ON again, the recovery mode is
deactivated automatically.
= flashing.
16
Disposal
|
(a)
7-segments display
Installer reference guide
275

Advertisement

Table of Contents
loading

Table of Contents