Radiant SiRRUS RHA 28 Design, Installation And Servicing Instructions

Gas fired, condensing boilers with storage cylinder

Advertisement

Quick Links

Installation and
Servicing Instructions
RHA 28
Gas Fired, Condensing Boilers
with Storage Cylinder
SEDBUK BAND B
CE
0694
TG05A062.A0205
RADIANT BRUCIATORI S.p.A. Montelabbate (PU) ITALY
ENGLISH

Advertisement

Table of Contents
loading

Summary of Contents for Radiant SiRRUS RHA 28

  • Page 1 Installation and Servicing Instructions RHA 28 Gas Fired, Condensing Boilers with Storage Cylinder SEDBUK BAND B 0694 TG05A062.A0205 RADIANT BRUCIATORI S.p.A. Montelabbate (PU) ITALY ENGLISH...
  • Page 3: Table Of Contents

    CONTENTS INSTALLATION INSTRUCTIONS PRODUCT CONFORMITY page INSTALLATION INSTRUCTIONS AND WARNINGS page TECHNICAL DATA page OVERALL DIMENSIONS page FLUE OPTIONS – FLUE KIT INSTALLATION INSTRUCTION page GENERAL INSTALLATION REQUIREMENTS page BOILER INSTALLATION page ELECTRICAL CONNECTIONS page SERVICING AND MAINTENANCE INSTRUCTIONS BOILER CONTROL PANEL page COMMISSIONING page...
  • Page 4 • GAS DIRECTIVE 92/42/ECC requirements for new hot-water boilers fired with liquid or gaseous fuels All RADIANT boilers are constructed according to UNI - CIG (EC) norms. The materials used, such as copper, brass, and stainless steel form a compact, homogeneous, highly functional unit that is easy to install and simple to operate. The wall-mounted boiler is equipped with all of the approved accessories required to make it a true, independent heating plant for home heating and for the production of hot water for domestic needs.
  • Page 5: Installation Instructions

    INSTALLATION INSTRUCTIONS_ INSTALLATION INSTRUCTIONS - WARNINGS THIS INSTALLATION, USE, AND MAINTENANCE MANUAL IS AN ESSENTIAL AND INTEGRAL PART OF THE PRODUCT, AND MUST ALWAYS BE KEPT NEAR THE DEVICE. THE WARNINGS CONTAINED IN THIS SECTION ARE ADDRESSED BOTH TO THE USER AND TO INSTALLATION AND MAINTENANCE PERSONNEL.
  • Page 6 INSTALLATION INSTRUCTIONS_ SYSTEMS WITH THERMOSTATS A by-pass must be installed in heating systems with radiators thermostats. As required by current norms, these devices must be installed by qualified personnel only, who must respect norms UNI-CIG 7129 and 7131 and revisions, fire department regulations, and requirements of the local gas company. Before installing the boiler, make sure that the water and heating systems are compatible with its output.
  • Page 7: Technical Data

    INSTALLATION INSTRUCTIONS_ RHA 28 Technical Data CE certification no. 0694BN3485 Flue category (UNI10642) Heat Input max kW (Btu/hr) 26.8 (91495) Heat Input min kW (Btu/hr) 20 (68280) Heat Output max (80/60°) kW (Btu/hr) 25.51 (87103) Heat Output max (50/30°) kW (Btu/hr) 27.47 (93783) Heat Output min (80/60°) kW (Btu/hr)
  • Page 8: Overall Dimensions

    INSTALLATION INSTRUCTIONS_ OVERALL DIMENSIONS 84.5 80 102 75.5 RETURN FLOW ¾” G GAS ½” HOT WATER ½” COLD WATER ½” HEATING FLOW ¾”Z SC CONDENSE DRAIN POINT CONDENSING WALL-HUNG BOILER – TG05A062.A0505...
  • Page 9: Flue Options - Flue Kit Installation Instruction

    (equivalent length): 2.5 metres – set the diaphragm 1 + remove tags NOTE: USE ORIGINAL RADIANT APPROVED FLUE KIT SYSTEMS, FLUE ACCESSORIES AND FLUE DIAPHRAGMS ONLY. APPROVED RADIANT FLUE DIAPHRAGMS AND ADJUSTMENT TABLES ARE SUPPLIED WITH RADIANT ORIGINAL FLUE KIT SYSTEMS.
  • Page 10 INSTALLATION INSTRUCTIONS_ OVERALL DIMENSIONS - FLUE KIT K KIT K: for the exhaust of combustion products and air intake through the 2 coaxial pipes, Ø100mm. external pipe (air intake) and Ø60mm. internal pipe (flue exhaust) to an external wall or a combined flue duct (chimney) conforming 7129/01 standard and D.P.R.
  • Page 11 (equivalent length): 2.5 metres – set the diaphragm 1.1; NOTE: USE ORIGINAL RADIANT APPROVED FLUE KIT SYSTEMS, FLUE ACCESSORIES AND FLUE DIAPHRAGMS ONLY. APPROVED RADIANT FLUE DIAPHRAGMS AND ADJUSTMENT TABLES ARE SUPPLIED WITH RADIANT ORIGINAL FLUE KIT SYSTEMS.
  • Page 12 INSTALLATION INSTRUCTIONS_ OVERALL DIMENSIONS - FLUE KIT H KIT H: for the exhaust of combustion products and air intake through the twin pipes Ø80mm/80mm. When deciding the Flue Length: consider the total length of flue starting room-seal chamber connection excluding the first bend. The use of additional bends reduce linear length by the following value:...
  • Page 13 (equivalent length): 2.5 metres – set the diaphragm 1 + remove tags NOTE: USE ORIGINAL RADIANT APPROVED FLUE KIT SYSTEMS, FLUE ACCESSORIES AND FLUE DIAPHRAGMS ONLY. APPROVED RADIANT FLUE DIAPHRAGMS AND ADJUSTMENT TABLES ARE SUPPLIED WITH RADIANT ORIGINAL FLUE KIT SYSTEMS.
  • Page 14 INSTALLATION INSTRUCTIONS_ OVERALL DIMENSIONS - FLUE KIT V KIT V = for the exhaust of combustion products and air intake through the 2 coaxial pipes, Ø100mm. external pipe (air intake) and Ø60mm. internal pipe (flue exhaust) to the roof conforming to UNI 7129/01 standard and D.P.R. 412/93 When deciding the Flue Length, consider the total length of flue starting by the room-seal chamber top connection.
  • Page 15: General Installation Requirements

    INSTALLATION INSTRUCTIONS_ GENERAL INSTALLATION REQUIREMENTS GAS SAFETY It is the law that all gas appliances are installed by a CORGI registered installer (you can check this by contacting corgi on 01256.372200) in accordance with the regulations listed below. Failure to install appliances correctly could lead to prosecution. It is in your own interest and that of safety to ensure that the law is complied with.
  • Page 16 INSTALLATION INSTRUCTIONS_ FLUE POSITION IMPORTANT: THE FLUE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE RECOMMENDATIONS CONTAINED IN BS 5440:1. The boiler MUST be installed so that the terminal is exposed to the external air. It is important that the position of the terminal allows free passage of air across it at all times. If the terminal discharges into a pathway or passageway check that combustion products will not cause nuisance and that the terminal will not obstruct the passageway.
  • Page 17 INSTALLATION INSTRUCTIONS_ CENTRAL HEATING SYSTEM -Fig. 1 The boiler is designed for use in a sealed central heating system in accordance with the requirements of BS 5449 and BS 6798. The system should be designed to operate with flow temperatures of up to 82°C. When designing the system, the pump head, expansion vessel size, mean radiator temperature, etc.
  • Page 18 INSTALLATION INSTRUCTIONS_ CONDENSATE DRAIN Termination to an internal soil and vent pipe FAILURE INSTALL CONDENSATE Boiler DISCHARGE PIPEWORK CORRECTLY WILL AFFECT THE RELIABLE OPERATION OF THE BOILER The condensate discharge pipe MUST NOT RISE at any point along its length. There MUST be a fall of AT LEAST 2.5°...
  • Page 19: Boiler Installation

    INSTALLATION INSTRUCTIONS_ BOILER INSTALLATION MINIMUM DISTANCES FOR FIXING TO WALL To allow access in the boiler for maintenance operations, the minimum distances shown below must be respected (fig. 1): To facilitate installation, the boiler is supplied with a template for advance location of connections to pipes.
  • Page 20 5th March ‘90 (see p.18). ANTI-FREEZE SYSTEM ANTI-FROST SYSTEM Circulating pump RSL 15/6-3 Radiant boilers are equipped with an Anti- Freeze system which comes into operation when the temperature falls to 5° C (Heating sensor) and 4° C (Hot water sensor).
  • Page 21: Electrical Connections

    INSTALLATION INSTRUCTIONS_ ELECTRICAL CONNECTIONS For qualified personnel only: the boiler works with 230 V 50 Hz AC current and has maximum input of 170 W. Connection to the electrical mains must be performed with a device having an omnipolar opening of at least 3 mm. Make sure the live and neutral connections conform to the diagram.
  • Page 22: Boiler Control Panel

    SERVICING AND MAINTENANCE INSTRUCTIONS_ CONTROL PANEL KEY TO CONTROLS (fig. 1) ON / OFF POWER BUTTON HEATING TEMPERATURE ADJUSTMENT KNOB DOMESTIC HOT WATER TEMPERATURE ADJUSTMENT KNOB OUTSIDE TEMPERATURE DISPLAY PAD (ONLY IF OPTIONAL OUTSIDE TEMPERATURE SENSOR IS FITTED) SERVICE PAD MODE SELECTION PAD (SUMMER ONLY / WINTER ONLY / SUMMER AND WINTER)
  • Page 23 SERVICING AND MAINTENANCE INSTRUCTIONS_ Filling the system After making sure the gas cock is closed, fill the heating system as follows; • fill the system until a pressure of 1 bar has been reached (light no. 11 ON; see AIR VENT VALVE CAP fig.
  • Page 24: Servicing And Maintenance Instructions

    SERVICING AND MAINTENANCE INSTRUCTIONS_ CONTROL PANEL ON / OFF POWER BUTTON WATER DEFICIENCY INDICATOR HEATING TEMPERATURE ADJUSTMENT KNOB WATER PRESSURE LEVEL 1 BAR INDICATOR DOMESTIC HOT WATER TEMPERATURE ADJUSTMENT KNOB WATER PRESSURE LEVEL 1.5 BAR INDICATOR GENERAL LOCK-OUT WITH FLASHING ERROR CODE ON MODE SELECTION PAD (SUMMER ONLY / WINTER ONLY / DISPLAY SUMMER AND WINTER)
  • Page 25: Technical Specifications

    SERVICING AND MAINTENANCE INSTRUCTIONS_ SM 20015 DIAGNOCODE ELECTRONIC PRINTED CIRCUIT BOARD cod. 76655LA TECHNICAL SPECIFICATION New generation printed circuit board with easy settings of boiler parameters. Special features: : Exclusively for technicians settings User settings • Standard / reduced heating temperature •...
  • Page 26 IT BRINGS THE HOT WATER TEMPERATURE OF THE STORAGE CYLINDER UP TO 60°C WHATEVER TEMPERATURE VALUE IS SET FOR HOT WATER. NOT COMPATIBLE THIS CODE IS DISPLAYED WHEN THE REMOTE CONTROL OR OUTSIDE REMOTE CONTROL. TEMPERATURE SENSOR CONNECTED ARE NOT ORIGINAL RADIANT PARTS. CONDENSING WALL-HUNG BOILER – TG05A062.A0505...
  • Page 27 SERVICING AND MAINTENANCE INSTRUCTIONS_ PARAMETERS TABLE PARAMETER PARAMETER TYPE OF OPERATION FUNCTION NUMBER VALUE WALL MOUNTED OR FLOOR STANDING BOILER TYPE SELECTION OIL FLOOR STANDING UNIT INSTANTANEOUS WITH STORAGE CYLINDER BOILER TYPE SELECTION WITH STORAGE CYLINDER-COMFORT 7°C) NATURAL GAS GAS TYPE SELECTION L.P.G.
  • Page 28 SERVICING AND MAINTENANCE INSTRUCTIONS_ Parameter setting: BOILER TYPE SELECTION To modify the Parameter value: a. Put ON/OFF button in OFF position ( b. Push pad simultaneously and keep them pressed; c. Put ON/OFF button in ON position ( and wait until the display shows d.
  • Page 29 SERVICING AND MAINTENANCE INSTRUCTIONS_ Parameter setting: HEATING TEMPERATURE SETTING To modify the Parameter value: a. Put ON/OFF button in OFF position ( b. Push pad simultaneously and keep them pressed; c. Put ON/OFF button in ON position ( and wait until the display shows d.
  • Page 30 SERVICING AND MAINTENANCE INSTRUCTIONS_ Parameter setting: WATER-HAMMER PREVENTION SETTING To modify the Parameter value: a. Put ON/OFF button in OFF position ( b. Push pad simultaneously and keep them pressed; c. Put ON/OFF button in ON position ( and wait until the display shows d.
  • Page 31 SERVICING AND MAINTENANCE INSTRUCTIONS_ Parameter setting: PUMP OVERRUN - HEATING CIRCUIT adjustable from 0 to 7.5 minutes. Factory calibrated at 3 minutes STANDBY. (N.B. DO NOT set the overrun time under 3 minutes) To modify the Parameter value: a. Put ON/OFF button in OFF position ( b.
  • Page 32 SERVICING AND MAINTENANCE INSTRUCTIONS_ : MECHANICAL MINIMUM GAS PRESSURE SETTING The mechanical minimum gas pressure is factory calibrated on all boilers at 17/18 mmH20. When replacing the gas valve adjust the mechanical minimum pressure as follows: : • Using a single cut screwdriver turn D screw (fig.1 ) clockwise and tight it ;...
  • Page 33 SERVICING AND MAINTENANCE INSTRUCTIONS_ MAXIMUM GAS PRESSURE SETTING - MAXIMUM HEATING OUTPUT SETTING Parameter setting: To check or modify the existing pressure value: a. Insert a manometer into the gas valve pressure point B (fig.1); b. Put ON / OFF button in OFF position ( c.
  • Page 34 SERVICING AND MAINTENANCE INSTRUCTIONS_ Parameter setting: MAXIMUM HEATING OUTPUT SETTING To check or modify the existing pressure value: a. Insert a manometer into the gas valve pressure point B (fig.1); b. Put ON/OFF button in OFF position ( c. Push pad simultaneously and keep them pressed;...
  • Page 35: Multigas Operation

    SERVICING AND MAINTENANCE INSTRUCTIONS_ CONVERSION OF GAS TYPE Conversion of the boiler from natural gas to LPG and viceversa must be performed by qualified personnel only. Conversion is performed as follows: Isolate the boiler from mains electricity supply Close the boiler gas service cock replace jets on the main Fig.
  • Page 36: Gas Pressure Setting

    SERVICING AND MAINTENANCE INSTRUCTIONS_ GAS DATA TABLE Natural Gas Liquid Butane Gas Liquid Propane Gas G 20 G 30 G 31 Lower Wobbe index (15°C; 1013 mbar) MJ/Nm 45.67 80.58 70.69 Rated feed pressure mbar Main burner: 13 Jets - Ø jet 1.25 0.77 0.77...
  • Page 37: Main Components

    SERVICING AND MAINTENANCE INSTRUCTIONS_ MAIN COMPONENTS POS. DESCRIPTION FLUE HOOD – ROOM SEALED COMBUSTION CHAMBER COMBUSTION CHAMBER ROOM SEALED CHAMBER COVER ROOM SEALED CHAMBER BACK HEAT EXCHANGER FLAT PLATE TYPE EXCHANGER MULTIGAS BURNER IGNITION ELECTRODE FLAME IONISATION ELECTRODE HEATING SAFETY THERMOSTAT ELECTRONIC GAS VALVE VK4105 ELECTRONIC IGNITION BOARD EXPANSION VESSEL...
  • Page 38 BOILER MAINTENANCE (carried out by Radiant Help Line) Every 12 months, or more frequently if the quality and consumption of water demand it, check the condition of the magnesium anode 1 and replace it if signs of wear are evident. To check the condition of the anode 2 (see fig. 2), open valve 4 on the top of the boiler, undoing the red knob in a clockwise direction.
  • Page 39: Wiring Diagrams

    SERVICING AND MAINTENANCE INSTRUCTIONS_ WIRING DIAGRAMS PRINTED CIRCUIT BOARD CVI-M SM20015 (cod. 76655LA) DISPLAY DIGITAL BOARD 2000 SKO6206 (COD. 76654LA) ELECTRONIC IGNITION BOARD - LINE CVI S4565 A 2019B (COD. 76631LA) - NEUTRAL - AIR PRESSURE SWITCH - WATER PRESSURE SWITCH - ELECTRONIC FLOWSWITCH Bloc - MAIN SWITCH...
  • Page 40 SERVICING AND MAINTENANCE INSTRUCTIONS_ WIRING DIAGRAM FOR REMOTE CONTROL INSTALLATION (no zone valves) Fig. 3 Interfaccia grey orange Fig. 2 P.B.C. INTERFACE REMOTE Fig. 4 EXTERNAL SENSOR M1 1 REMOTO Fig. 5 Fig. 1 Fit the interface (fig. 2) on the circuit board (fig. 1) into the holes A and B provided (see fig. 1). Connect plug M1 on the interface circuit board (fig.
  • Page 41: Maintenance

    SERVICING AND MAINTENANCE INSTRUCTIONS_ MAINTENANCE Casing removing • pull and remove the boiler front casing; • undo the 4 bottom screws that fix the side casing to the lower boiler grid (2 screws each side panel); • undo the casing fixing plate screw on the left side of the room seal chamber; •...
  • Page 42: Fault Finding Chart

    SERVICING AND MAINTENANCE INSTRUCTIONS_ Fault Description Possible Cause Solution Code BOILER FAILS TO FIRE No gas / gas turned off Check gas supply / open the gas cock Ignition electrode damaged or earthed Replace it Electronic ignition board S4565QM faulty Replace it Gas valve faulty Replace it...
  • Page 43: Short List

    SERVICING AND MAINTENANCE INSTRUCTIONS_ SPARE PARTS SHORT LIST CODE DESCRIPTION RHA 28 √ 20025LA ANODE W/CONTROL VALVE √ 20040LA PLATE EXCHANGER 561222 20051LA CYLINDER LT.14 1132710 √ √ 21001LA GAS BURNER 13 RAMP 1.25 NATURAL GAS 401.1207.02 √ 21004LA GAS BURNER 13 RAMP 0,77 L.P.G. 401.1207.02 24046LA CIRCULATING PUMP RSL 15/6-3-KU CLF6 W/C1-C3 √...
  • Page 44 SERVICING AND MAINTENANCE INSTRUCTIONS_ MULTIPLEX - SPARE PARTS SHORT LIST 43150LA 64066LA 43139LA 54022LA 89116NA 89116NA 64065LA 20040LA 43135LA 64069LA 89122NA 89122NA 43150LA 43145LA 43150LA 43151LA 64063LA 61004LP 64075LA 54023LA 64061LA 43139LA 43139LA 43150LA 54022LA 43150LA 43150LA 43159LA 54022LA 43139LA 96034LA 54024LA 54022LA...
  • Page 48 RADIANT BRUCIATORI s.p.a. Via Pantanelli, 164/166 - 61025 Loc. Montelabbate (PU) Tel. +39 0721 9079.1 • fax. +39 0721 9079279 e-mail: info@radiant • Internet: http: www.radiant.it UK – Radiant Helpline – 01329.828555 ALL DESCRIPTIONS AND ILLUSTRATIONS CONTAINED IN THIS LEAFLET HAVE...