Installation and Maintenance Manual for model R2K 34 RAIN Condensing boiler with integrated heat exchanger for domestic hot water side, suitable for outdoor installation R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
2.1.5. DIGITECH CS PARAMETERS TABLE 2.1.6. ELECTRIC FAN FREQUENCY/HEAT CAPACITY DIAGRAM 2.2. MAINTENANCE 2.2.7. GENERAL MAINTENANCE WARNINGS 2.2.8. TECHNICAL DATA 2.2.9. TECHNICAL ASSEMBLY 2.2.10. HYDRAULIC BOARD 2.2.11. 3-WAY VALVE OPERATION 2.2.12. WIRING DIAGRAM R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 4
TABLE OF CONTENTS 2.2.13. ACCESSING THE BOILER 2.2.14. ACCESSING THE ELECTRONIC BOARD 2.2.15. SYSTEM EMPTYING 2.2.16. FAULT SIGNALLING CODES 2.2.17. ACTIVE FUNCTIONS SIGNALLING CODES 2.2.18. GAS CONVERSION R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
DO NOT PLACE ARTICLES ON OR AGAINST THIS another section in the Manual that you should APPLIANCE. refer to. DO NOT MODIFY THIS APPLIANCE. › Device: this term is used referring to the boiler. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 6
› the material and intellectual ownership of this manual and forbids its distribution and duplication, even partial, without prior written authorization. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
1. INSTALLER SECTION 1. INSTALLER SECTION The installation operations described in this section should be performed only by qualified personnel, having the appropriate technical training in the field for the installation and maintenance of components of civil and industrial domestic hot water production and heating plants.
› The location must be properly vented through an avoid that the combustion air is exposed to chlorine, air vent. ammonia or alkaline agents that may worsen the corrosion phenomenon of the heat exchanger. Failure R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
AS/NZS 5601 – Gas installations (installation and pipe sizing), local gas fitting regulations, local electrical regulations, local water regulations, local health regulations, Building Code of Australia and any other government authority. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
› Turn the boiler at 90° holding it with your hand (fig. 1-B). › Lift the box (fig. 1-C) and remove the guards (fig. 1-D). fig. 1 R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
X - 60 mm fig.1 It is allowed an outdoor installation in a partially protected location (i.e. shelter, balcony) that respect the minimum measure indicated in figure 2. 1200 mm R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 12
R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
This is just a air purge function and will last for commissioning mins. (Please Allow This Cycle To Finish) “Refer to Pg 31 for more details” “Refer to Pg 22 for more details” Control Panel R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
The company assumes no liability for plant overpressure. damage caused to persons or for failure to comply with these instructions. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
3 the loading tap “R” (fig. 2) is properly closed. Unscrew the circulator cap (2-fig.1) to release any air bubbles and close it to prevent water leakage; R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
› Connect the dedicated flexible condensate draining tube to a waste disposal system. The condensate can be drained directly in the sewerage system by inserting an easily serviceable siphon. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
If the temperature goes below -10° centigrades, please fill the plant with anti-freeze liquid (CLEANPASS FLUIDO AG cod. 98716LA) and insert and electrical resistances kit (cod. 82259LP). R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
WARNING It is strictly forbidden the use of adaptors, multiple plugs and/or extensions for the general power supply of the equipment from the electrical network. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
· the blue cable to the terminal marked with “N”. · the brown cable to the terminal marked with “L”. After performing these operations, remount plate “A” and the front casing. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
“A” and the front casing. establishing the connection, the used interface on the board is disabled and the display shows the symbol ‘ ’. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 23
TAZ1: ENVIRONMENT THERMOSTAT AREA 1 ORANGE TAZ 2: ENVIRONMENT THERMOSTAT AREA 2 BLACK VZ1: AREA 1 VALVE BROWN VZ2: AREA 2 VALVE LIGHT BLUE VZR: REMOTE CONTROLLED AREA VALVE R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
› In order to discharge the fumes through a fumes exhaust duct carefully follow the technical standards in force. INSTALLATION REQUIREMENTS For Australia – refer to AS/NZS 5601 and local authority for minimum clearances as illustrated below: R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 25
1. INSTALLATION R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Subsequent addition of a curve is similar to adding a linear length of tube according to the indications below: co-axial curve Ø80 to 90° = 1.5 m co-axial curve Ø80 to 45° = R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 27
Subsequent addition of a curve is similar to adding Ø80 a linear length of tube according to the indications below: co-axial curve Ø80 to 90° = 1.5 m co-axial curve Ø80 to 45° = R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 28
PLEASE NOTE: during the flue analysys tests, place the analyser inside the frontal flue kit terminal slots. SECTION A-A R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
2. SUPPORT CENTRE SECTION All operations described below relative to first start- up, maintenance and replacement should be performed only by qualified personnel and authorized by RADIANT BRUCIATORI S.p.A. Gas leakage and operation of the appliance must be tested by the installer before leaving. When satisfied with the operation, please instruct the consumer on the correct method of operation.
Local and National Laws and Standards; › make sure that the heating system gate valves are open; › make sure that there is no intake of gaseous products within the system; R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
2 minutes. Throughout this function the display will show the code “F33”. The boiler can work normally only after completing the operation. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
› After each adjustment variation on screw ‘1’ (fig. 2) of the gas flow adjuster you have to wait for the boiler to stabilize itself to the set value (about 30 seconds). R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
’with the message ‘P00’, and release the keys ‘ ’ and ‘ ’. Use the keys ‘ ’ and ‘ ’ of the heating circuit to select the parameter to be edited. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 34
To exit the parameters menu, hold at the same time the keys ‘ ’ and ‘ ’ and wait for the symbol ‘ ’ to appear on the display. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
0 - 5 0 = ISTANTANEOUS R2K 1 = ISTANTANEOUS RKR 2 = ACCUMULATION 3 = ACCUMULATION COMFORT 4 = ISTANTANEOUS COMFORT - FAST H2O 5 = HEATING ONLY R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 36
THROUGH THIS PARAMETER YOU CAN SET THE MINIMUM TIME FOR WHICH IN MULTIPLES OF 5 THE BURNER WILL BE TURNED OFF ONCE THE HEATING TEMPERATURE SECONDS REACHED THE USER SET TEMPERATURE. (PRE-SET AT 36 X 5 = 180 SECONDS) R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 37
DURING A REQUEST TO OPERATE IN HEATING MODE. [SEE CHAPTER ‘HEAT CAPACITY DIAGRAM (KW) – ELECTRIC FAN FREQUENCY (HZ)’]. THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER P02) R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 38
SUCH DOMESTICH HOT WATER TREATMENT (AND INFORM THE USERS) TO AVOID UNFORSEEABLE DAMAGES TO PERSONS, ANIMALS AND PROPERTY. A THERMOSTATIC VALVE SHOULD BE INSTALLED AT THE DOMESTIC HOT WATER OUTLET TO AVOID ANY BURNS. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 39
FOR DOMESTIC HOT WATER, THE FLOW SWITCH AND THE BOILER WILL TURN ON. EXAMPLE 2: WITH THE BOILER CLOCK SWITCH CLOSE, UPON THE REQUEST FOR DOMESTIC HOT WATER, THE FLOW SWITCH AND THE BOILER WILL NOT TURN ON. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 40
(FOR STORAGE BOILERS ONLY) IN °C (PRE-SET AT 9°C) THROUGH THIS PARAMETER YOU CAN SET THE PRIORITY STARTING VALUE OF THE STORAGE TANK, COMPARED TO THE USER ADJUSTABLE D.H.W SETPOINT. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 41
THE VALUE IS EXPRESSED THROUGH THIS PARAMETER, IT IS POSSIBLE TO SET THE HEATING WATER IN °C (SET BY DEFAULT TEMPERATURE AT WHICH THE ANTI-FREEZE PROTECTION DEVICE STARTS AT 8 °C) WORKING. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
2. FIRST START-UP 2.1.6. ELECTRIC FAN FREQUENCY/HEAT CAPACITY DIAGRAM Natural Gas (Black) Propane only (Orange) FREQUENCY (Hz) GAS TYPE MINIMUM FREQUENCY MAXIMUM FREQUENCY Natural Gas (Black) Universal LPG (Orange) R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
› remove and clean the burner from oxidation; or neutralization devices for acid condensate. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 45
2. MAINTENANCE › check that the liquid flow is not obstructed and that there are no combustion gas refluxes inside the internal system. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Specific capacity in continuous service - Δt 30°C litres/min Dimensional characteristics Width Depth Height Gross weight Water connections Flow Ø 3/4” Cold water Ø 1/2” Hot water Ø 1/2” Ø 3/4” R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 47
Heating Max. fan speed - Universal LPG D.H.W Max fan speed - Universal LPG Heating Min. fan speed - Universal LPG D.H.W Min. fan speed - Universal LPG Fuel consumption - Universal LPG MJ/h R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
AIR RELIEF VALVE CIRCULATOR SAFETY VALVE 3 bar SYSTEM DRAINING TAP 10. GAS VALVE 11. DOMESTIC CIRCUIT PROBE 12. SAFETY THERMOSTAT 13. HEATING PROBE 14. EXPANSION TANK 15. AIR SUCTION TUBE R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
(see ‘C’ - fig. 1). › The RED color (with C-A) indicates the operation in the Domestic Hot water mode. › The BLUE color (with C-B) indicates the operation in Heating mode. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
› remove the fastening screws (5) placed on the front edge of the side panel; › grab the bottom of the panel, and remove it by moving it sideways and pulling it upwards. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
(fig. 1) loosening them and turn the panel downwards; › unscrew the four fastening screws 1 - fig. 1; › remove the crankcase pulling it upwards. fig. 1 R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
› close the main supply tap of the water supply network; › open all cold and hot water taps; › after completing all operations, close the discharge tap and all previously opened water taps. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
IF THE TENSION MEASURES BETWEEN PHASE-PHASE NEUTRAL AND GROUND IS ALMOST EQUAL TO THE ONE MEASURED BETWEEN PHASE AND GROUND, YOU HAVE TO INSTALL A PHASE-PHASE TRANSFORMER KIT (COD. 88021LA) R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 56
THE FLOW RATE VALUE INCREASE THE FLOW RATE OR LOWER AUTOMATIC. DETECTED BY THE THE VALUE AT PARAMETER P33. FLOWMETER IS LOWER THAN THE VALUE SET AT PARAMETER P33. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 57
REMOTE CONTROL IS NOT COMPATIBLE WITH THE P.C.B. COMMUNICATION ERROR NO ELECTRICAL CHECK THE WIRING; AUTOMATIC. BETWEEN THE BOILER CONNECTION; BOARD AND THE MODBUS BOARD MODBUS BOARD BROKEN; REPLACE IT; R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
Page 58
SUPPLY VOLTAGE FALLS BACK WITHIN THE REQUESTED LIMITS). COMMUNICATION FAULT NO ELECTRICAL CHECK THE WIRING; AUTOMATIC. BETWEEN MODBUS CONNECTION; CONTROLLER AND MODBUS CONTROL UNIT MODBUS CONTROL UNIT REPLACE IT; BROKEN. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
YOU CAN ACTIVATE/DEACTIVATED IT BY HOLDING SIMULTANEOUSLY AND FOR 7 SECONDS THE RESET ‘ ’ AND ‘ ’ OF THE DOMESTIC CIRCUIT . THE “FAST H2O” FUNCTION GUARANTEES THE IMMEDIATE D.H.W SUPPLY AT THE REQUESTED TEMPERATURE. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...
TYPE SELECTION’ from the control panel (see fig. 3 chapters ‘DIGITECH CS PARAMETERS TABLE’ and ‘ACCESSING AND PROGRAMMING THE PARAMETERS’); › adjust the CO2 combustion value as indicated in chapter ‘CO2 VALUE CHECK AND CALIBRATION’. R2K 34 RAIN - RAD - ING - Man.Inst. - 1901.1_V3_firm.L224C_AHS...