Sanyo SAP-K71GJA-S Technical & Service Manual page 48

Table of Contents

Advertisement

B. Circuit breaker trips in several minutes after turning the air conditioner on.
There is a possibility of short circuit.
Check capacity of circuit breaker.
Capacity of circuit breaker is
suitable.
Measure resistance of outdoor fan
motor winding.
Measure resistance of compressor
motor winding.
9-2-2. Neither indoor nor outdoor unit runs.
A. Power is not supplied.
• Check power supply.
Power is being supplied to the
outdoor unit.
B. Check remote control unit.
• Try to run with another remote
control unit.
First remote control unit is defective.
• Check for residue buildup on
transmitter of remote control unit.
• Check for residue buildup on remote
control receiver on front of indoor
unit.
NO
NO
Does not run.
OK
Replace with suitable
one (larger capacity).
Circuit breaker
is tripped.
Power failure
Refer to Step C below.
Clean transmitter.
Clean receiver.
45
Reset breaker.
Wait for recovery
or contact power
company.

Advertisement

Table of Contents
loading

Table of Contents