3.3.6 Indoor and Outdoor Shelter Exhaust
Conversion
For both Category I and Category III vent types the
heater must fi rst be converted to an indoor exhaust
type. In order to complete the conversion you will
need to order exhaust conversion R-Kit R0731100.
a
Remove two screws securing the exhaust grill to
the exhaust grill backplate.
b
Remove exhaust
grill.
c
Remove the two
screws securing the
rain shield to the
exhaust backplate.
d
Remove the rain
shield.
e
Remove the
remaining two screws
securing the exhaust
backplate to the
exhaust outlet.
f
Remove the exhaust grill backplate.
g
Using two #10 thread cutting screws secure the
vent adapter from R-Kit R0731100 to the exhaust
outlet.
h
If venting for Category I, install an appropriate
vent pipe increaser to accommodate the correct pipe
size from Table 1. Secure to the vent adapter using
the screw clamp.
When the installation requires horizontal venting in
excess of what is allowed for Category I installations
or calls for horizontal discharge, the JXi may be
installed with a Category III venting system.
Vent the heater either vertically or horizontally
using Al29-4C stainless steel components. Consult
manufacturers such as Z-Flex
obtain approved components. Venting materials
must comply with UL
®
Special Gas Vent. Based on the normally
expected fl ue temperatures of this
appliance. PLASTIC VENTING MUST
NOT BE USED.
i
If venting for Category III, install
appropriate vent pipe from Table 1. Secure
to the vent adapter using the screw clamp to
ensure a proper seal.
Page 18
a
a
or Heat Fab
to
®
®
1738 for Category III,
4" Vent Pipe
Jandy
JXi
Gas-Fired Pool and Spa Heater | Installation & Operation Manual
®
Double check that there are no possible leak
paths between joints. If a leak path is identifi ed or
suspected it can be sealed using red RTV 600° F
rated silicone adhesive.
When using parts or materials from other
manufacturers please be sure to follow the
manufacturers instructions completely to ensure
harmonious function.
Exhaust Outlet
Exhaust Grill
Backplate
Rain Shield
Exhaust Grill
c
e
b
IMPORTANT NOTE:
Massachusetts, additional requirements, covered
in document CMR 248 5.00, which supersede
some of the requirements of ANSI Z223.1 (NFPA
54) apply to Side Wall Horizontally Vented
appliances. If installing this product using an
approved side-wall horizontal vent system in the
Commonwealth of Massachusetts, be sure to
adhere to these additional requirements. These
requirements include verbiage that says that
the property owner is to ensure that Carbon
Monoxide Detectors are installed in the vicinity of
the appliance and also on all levels of the dwelling
in which the appliance is installed.
For further instructions, contact Technical
Support at 800.822.7933.
Exhaust Outlet
Vent Elbow
Vent Adapter
Increaser
h
y I
t e g o r
f o r C a
O R
I I I
t e g o r y
f o r C a
f
d