Adjustments Prior To Ignition (Gas); Burner Start-Up (Gas); Check Motor Rotation; Burner Ignition - Riello RLS 1000/E MX Installation, Use And Maintenance Instructions

Dual fuel gas oil/gas burners modulating operation
Table of Contents

Advertisement

6.4

Adjustments prior to ignition (gas)

In addition, the following adjustments must also be made:
 slowly open the manual valves situated upstream from the
gas train.
 Adjust the minimum gas pressure switch (Fig. 37, a pag. 33)
to the start of the scale.
 Adjust the maximum gas pressure switch (Fig. 36, a
pag. 33) to the end of the scale.
 Adjust the air pressure switch (Fig. 35, a pag. 33) to the start
of the scale.
 Purge the air from the gas line.
We recommend using a plastic tube routed outside the build-
ing and to purge air until gas is smelt.
 Fit a U-type pressure gauge or a differential pressure gauge
(Fig. 33), with socket (+) on the gas pressure of the pipe
coupling and (-) in the combustion chamber.
The manometer readings are used to calculate MAX burner
output.
 Connect two lamps or testers to the two gas line solenoids to
check the exact moment in which voltage is supplied.
This operation is unnecessary if each of the two solenoid
valves is equipped with a pilot light that signals voltage pass-
ing through.
6.5

Burner start-up (gas)

Close the remote controls and position the selector 1)(Fig. 32) to
"AUTO".
Position the selector 2) to "GAS" to select gas as fuel.
Make sure that the lights or testers connected to the solenoids, or
the pilot lights on the solenoids themselves, indicate that no volt-
6.6

Check motor rotation

As soon as the burner starts up, go in front of the
fan motor cooling fan and check it is rotating anti-
clockwise (Fig. 34).
WARNING
If this is not the case:
 turn the burner switch to position "0" (OFF) and wait for the
control box to carry out the switch-off phase;
 disconnect the power supply to the main panel;
 invert the phases on the three-phase power supply;
 if necessary, carry out the same operation for the pump
motor.
This operation must be carried out with the electri-
cal supply disconnected.
DANGER
6.7

Burner ignition

The burner should light after having performed the above steps.
If the motor starts up, but the flame does not appear and the con-
trol box goes into lockout, reset it and wait for a new ignition at-
tempt.
If ignition is still not achieved, it may be that gas is not reaching
the combustion head within the safety time period of 3 seconds.
In this case increase gas ignition delivery.
Start-up, calibration and operation of the burner
Before starting up the burner, it is good practice to
adjust the gas train so that ignition takes place in
conditions of maximum safety, i.e. with gas deliv-
ery at the minimum.
CAUTION
20053397
age is present. If voltage is present, stop the burner immediately
and check the electrical connections.
When the limit thermostat (TL) closes, the "CALL FOR HEAT" 3)
signal must come on. The burner will subsequently begin its start-
ing cycle.
The arrival of gas at the sleeve is indicated by the U-type manom-
eter (Fig. 33).
If further burner lockouts occur, refer to the "Release procedure"
given in the equipment manual supplied.
31
GB
20079199
Fig. 33
Fig. 34
20061317

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rls 1200/e mx2005752920057530

Table of Contents