Nozzle Installation; Recommended Nozzle - Riello RLS 1000/E MX Installation, Use And Maintenance Instructions

Dual fuel gas oil/gas burners modulating operation
Table of Contents

Advertisement

5.9

Nozzle installation

The burner complies with the emission requests specified in
standard EN 267. To guarantee a constant level of emissions, it
is necessary to use the nozzles recommended and/or alterna-
tives indicated by Riello in the instructions and warnings.
It is advisable to replace the nozzle once a year
during periodical maintenance.
WARNING
The use of nozzles other than those specified by
Riello S.p.A. and inadequate regular maintenance
may result into emission limits non-conforming to
the values set forth by the regulations in force, and
in extremely serious cases, into potential hazards
to people and objects.
CAUTION
The manufacturing company shall not be liable for
any such damage arising from nonobservance of
the requirements contained in this manual.
Fit the nozzle with a 24 mm (for RLS 1000/E MX) and 41 mm (for
RLS 1200/E MX) box wrench, passing from the centre opening of
the flame stability disc (Fig. 14).
Fit the nozzles with the fuel interception rod on the nozzle holder.
To calibrate the delivery range of operation of the nozzle, adjust
the fuel pressure on the nozzle return line, according to Tab. H.
 Do not use any sealing products such as gas-
kets, sealing compound, or tape.
 Be careful to avoid damaging the nozzle seal-
ing seat.
WARNING
 The nozzle must be screwed into place tightly
but not to the maximum torque value pro-
vided by the wrench.
D11310
Installation
5.9.1
Model
RLS 1000/E MX
RLS 1200/E MX
Complete range of nozzles:
11. 4 mm
Fig. 14
19
GB

Recommended nozzle

Nozzle
Bergonzo
Fluidics
Bergonzo
Bergonzo type B5 60°
350 - 375 - 400 - 425 - 450 - 475 - 500 - 525 - 550 - 575 - 600
650 - 700 - 750 - 800 - 850 - 900.
Bergonzo type C3 - C5 60°
700 - 800 - 900 - 1000 - 1100
Fluidics type W2 60°:
375 - 400 - 450 - 500 - 550 - 600 - 650 - 700 - 750.
Delivery
kg/h
pressure
pressure
(bar)
18
350
20
20
600
22
20
750
22
16
900
20
18
700
20
18
700
20
17
900
18
16
1100
18
type B5 60°
type W2 60°
type C3 - C5 60°
Return
kg/h
kW
(bar)
8
100
1200
17.5
315
3750
6
140
1675
16
563
6700
6.5
180
2150
19
722
8600
4
168
2000
15
867
10300
3
172
2043
16
462
5500
3
172
2043
19
635
7550
5
237
2815
17.5
791
9400
6
273
3242
16.5
961
11425
20061317
Tab. H

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rls 1200/e mx2005752920057530