Technical data

Model
Type
Output
(1)
min - max
Delivery
(1)
Fuels
Gas pressure at max. output
Gas: G20/G25
Operation
Pump
Output at 30 bar
Pressure range
Fuel temperature
Nozzles
Standard applications
Ambient temperature
Combustion air temperature
Noise levels
Sound pressure
(3)
Sound power
Weight
Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(1)
Pressure on the test point with zero pressure in the combustion chamber and at maximum burner output.
(2)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output. The sound
(3)
power is measured with the "Free Field" method, as per EN 15036, and according to an "Accuracy: Category 3" measuring accuracy, as set out in
EN ISO 3746.
4.5

Electrical data

Model
Electrical supply
Fan motor IE3
Pump motor
Ignition transformer
Electrical power consumption Light oil
Protection level
4.6

Burner categories - Countries of destination

Country of destination
AT - BG - CH - CZ - DK - EE - ES - FI - GB - GR - HU - IE - IS - IT - LT -
LV - NO - PT - RO - SE - SI - SK - TR
20061317
Technical description of the burner
kW
kg/h
-
(2)
mbar
kg/h
bar
°C max
number
°C
°C max
dB(A)
kg
rpm
Hz
V
kW
A
rpm
V
kW
A
V1 - V2
I1 - I2
kW max
Gas
DE
NL
FR
BE
LU - PL
RLS 1000/E MX
1311 T1
1200/3750 ÷ 10600
100/315 ÷ 867
Light oil, max. viscosity at 20 °C: 6 mm
Natural gas: G20 (methane gas) - G21 - G22 - G23 - G25
67.8/101.1
Intermittent (min. 1 stop in 24 hours)
Modulating
1400
9/40
140
Boilers: water, steam, diathermic oil
85.4
100.6
500
RLS 1000/E MX
2950
50
400/690
22
39.4/22.7
1458
230/400
2,2
9.3/5.4
27
24
8
GB
RLS 1200/E MX
1312 T1
1500/5500 ÷ 11500
171/462 ÷ 942
2
/s (1.5 °E - 6 cSt)
97.2/145
1826
9/40
140
1
0 - 50
60
84.4
99.7
540
RLS 1200/E MX
3N ~ 400V 50 Hz
2930
400/690
44/25.4
1400
400
8.2
230 V - 1 x 8 kV
1 A - 20 mA
27.2
IP 55
Gas category
I
2H
I
2ELL
I
2EK
I
2Er
I
2E(R)
I
2E
Tab. A
50
25
4
32
Tab. B
Tab. C

Advertisement