ABB RELION RED670 Series Product Manual page 77

Line differential protection
Hide thumbs Also See for RELION RED670 Series:
Table of Contents

Advertisement

Line differential protection RED670 2.2
Product version: 2.2
Table 42. Phase selection, quadrilateral characteristic with settable angle FRPSPDIS
Function
Minimum operate current
Reactive reach, positive
sequence
Resistive reach, positive
sequence
Reactive reach, zero sequence
Resistive reach, zero sequence
Fault resistance, Ph-E faults,
forward and reverse
Fault resistance, Ph-Ph faults,
forward and reverse
Reset ratio
ABB
GUID-9E13C38A-3B6D-402B-98A6-6CDA20632CE7 v5
Range or value
(5-500)% of IBase
(0.50–3000.00) Ω/phase
(0.10–1000.00) Ω/phase
(0.50–9000.00) Ω/phase
(0.50–3000.00) Ω/phase
(1.00–9000.00) Ω/loop
(0.50–3000.00) Ω/loop
105% typically
Accuracy
±1.0% of I
at I ≤ I
r
r
±1.0% of I at I > I
r
±2.0% static accuracy
±2.0 degrees static angular accuracy
Conditions:
Voltage range: (0.1-1.1) x U
r
Current range: (0.5-30) x I
r
Angle: at 0 degrees and 85 degrees
-
1MRK 505 379-BEN C
77

Advertisement

Table of Contents
loading

Table of Contents