ABB RELION RED670 Series Product Manual page 65

Line differential protection
Hide thumbs Also See for RELION RED670 Series:
Table of Contents

Advertisement

Line differential protection RED670 2.2
Product version: 2.2
The stated operate time for functions
include the operating time for the binary
inputs and outputs.
Table 21. BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity
Binary outputs
Max system voltage
Test voltage across open contact, 1 min
Current carrying capacity
Per relay, continuous
Per relay, 1 s
Per process connector pin, continuous
Making capacity at inductive load with L/R > 10 ms
0.2 s
1.0 s
Breaking capacity for AC, cos j > 0.4
Breaking capacity for DC with L/R < 40 ms
Operating time
The stated operate time for functions
include the operating time for the binary
inputs and outputs.
Influencing factors
Table 22. Temperature and humidity influence
Parameter
Ambient temperature, operate
value
Relative humidity
Operative range
Storage temperature
ABB
M16705-1 v15
Reference value
+20°C
10-90%
0-95%
-
Nominal range
-25°C to +55°C
10-90%
-40°C to +70°C
1MRK 505 379-BEN C
Trip and Signal relays
24
250 V AC, DC
1000 V rms
8 A
10 A
12 A
30 A
10 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
< 6 ms
Influence
0.02%/°C
-
-
M12441-1 v9
IP15846-1 v1