Siemens RUGGEDCOM WIN5123 Installation Manual page 37

Hide thumbs Also See for RUGGEDCOM WIN5123:
Table of Contents

Advertisement

RUGGEDCOM WIN5123
Installation Guide
Test
IEC-60068-2-14
IEC 60068-2-30
IEC 60068-2-18
IEC 529 (IP65/IP67)
IEC-60068-2-64
Class 4M5
IEC-60068-2-29
Class 4M5
IEC-60068-2-1
IEC-60068-2-2
IEC-60068-2-14
IEC 60068-2-30
IEC 60068-2-18
IEC-60068-2-64
IEC-60068-2-29
IEC-60068-2-32
Nebs: GR63
IEC-60068-2-1
Environmental Type Tests
Description
TEMP CHANGE
HUMIDITY (Cycling)
WATER: Rain (intensity)
RANDOM
VIBRATION (4M5)
SHOCK (4M5)
LOW TEMP
HIGH TEMP
TEMP CHANGE
HUMIDITY (Cycling)
WATER: Rain
RANDOM
VIBRATION
SHOCK
FREE FALL
LOW TEMP
Test Levels
Duration: 16h
-10 to 45 °C
0.5 °C/min
Duration: 2 cycles
30°C 90-100%
Duration: 2 cycles
0.01m3/min, 90kPa, 30min
ASD - 0.04 m²/s3³
12 -12 dB /oct
Freq. Range 5-10, 10-50, 50-100 Hz
3 Axes
Duration: 30min each axes
Spectrum: Half sine
Duration: 11 ms
Accelerator: 50 m/s²
100 shocks in each direction
-40 °C
Duration: 72h
70 °C
Duration: 72h
-40 -30 °C
1 °C/min
Duration: 5 cycles
40°C, 90-100%
Duration: 2 cycles
0.01 m³/min, 90 kPa
Duration: 15 min.
ASD - 1 m²/s³
-3 dB /oct
Freq. Range: 5-20 Hz
20-200
3 Axes
Duration: 30min each axes
Spectrum: Half sine
Duration: 6 ms
Accelerator: 180 m/s²
100 shocks in each direction
Height: 1m
One fall on 3 faces, 3 edges and 4 corners
-25 °C
Chapter 5
Certification
31