Lochinvar EcoCharger ECH 32-220 G CE Installation, Commissioning, User & Maintenance Instructions page 106

Gas fired condensing water heater
Table of Contents

Advertisement

Description
Gas category 2H: G20
Diameter of the venturi
restrictor
Nominal Load (gross)
Nominal output
Supply pressure
CO
(full load)
2
O
(full load)
2
Gas consumption
(1)
NO
-emission
x
Mass flow rate flue gases
(minimal load)
Mass flow rate flue gases
(nominal load)
Flue gas temperature
(nominal load)
Gas category 3P: G31
Diameter of the venturi
restrictor
Nominal Load (gross)
Nominal output
Supply pressure
Gas control valve pressure
CO
(full load)
2
O
(full load)
2
Gas consumption
NO
-emission
x
Mass flow rate flue gases
(minimal load)
Mass flow rate flue gases
(nominal load)
Flue gas temperature
(nominal load)
1 - Based on 1013.25 mbar and 15°C.
106
Unit
ECH 87-480
mm
8.60
kW
88.1
kW
85.7
mbar
20
vol%
8.9 ± 1.0
vol%
5.0 ± 1.8
3
8.3
m
/h
mg/kWh GCV
34
kg/h
52.8
kg/h
141.9
ºC
52
mm
6.60
kW
86.2
kW
85.7
mbar
37 / 50
mbar
-
vol%
9.6 ± 1.0
vol%
6.3 ± 1.8
kg/h
6.1
mg/kWh GCV
38
kg/h
53.5
kg/h
149.1
ºC
52
ECH 106-480
ECH 129-480
8.60
8.60
107.3
131.0
102.4
123.9
20
20
8.9 ± 1.0
8.9 ± 1.0
5.0 ± 1.8
5.0 ± 1.8
10.1
12.3
36
37
52.8
52.8
172.9
211.1
55
60
6.60
6.60
105.7
128.2
102.4
123.9
37 / 50
37 / 50
-
-
9.6 ± 1.0
9.6 ± 1.0
6.3 ± 1.8
6.3 ± 1.8
7.4
9.0
39
39
53.5
53.5
181.6
221.7
55
60
Installation, Maintenance and Service part