Figure 4-2 Controller Operation -- Perishable Mode - Carrier 69NT20-551-300 TO 399 Operation And Service

Container refrigeration units
Table of Contents

Advertisement

c.The 30 minute timer will be reset at each of the follow-
ing conditions:
1. At every power up.
2. At the end of every defrost.
3. After every diagnostic check that does not fall out-
side of the limits as outlined above.
d. Probe Check
A defrost cycle probe check is accomplished by
energizing just the evaporator motors for eight minutes
at the end of the normal defrost. At the end of the eight
minute period the probes will be compared to a set of
predetermined limits. The defrost indicator will remain
on throughout this period.
PULL DOWN
START UNLOADED,
TRANSITION TO
ECONOMIZED
OPERATION
UNLOADED OPERATION
AIR CIRCULATION
HEATING
NOTE: TEMPERATURES INDICATIONS ARE ABOVE OR BELOW SET POINT
T-322
FALLING
TEMPERATURE
+2.5_C
(4.5_F)
MODULATED
UNLOADED
+.20_C
SET POINT
- -0.20_C
AIR CIRCULATION
- -0.5_C
(0.9_F)
Figure 4-2 Controller Operation - - Perishable Mode
Any probe(s) determined to be outside the limits will
cause the appropriate alarm code(s) to be displayed to
identify which probe(s) needs to be replaced. The P5
Pre-Trip test must be run to inactivate alarms.
4.9 SEQUENCE OF OPERATION
General operation sequences for cooling, heating and
defrost are provided in the following subparagraphs.
Schematic representation of controller action are
provided in Figure 4-2 and Figure 4-3. Refer to Section
3 for detailed descriptions of special events and timers
that are incorporated by the controller in specific modes
of operation.
+2.5_C
(4.5_F)
COOLING
+.20_C
SET POINT
- -0.20_C
- -0.5_C
(0.9_F)
HEATING
4-4
RISING
TEMPERATURE
MODULATED
COOLING
UNLOADED
AIR CIRCULATION
HEATING