Carrier 59SC6A Installation Instructions Manual page 47

Single-stage, high efficiency, 4-way multipoise 35-in. (889 mm), condensing gas furnace
Table of Contents

Advertisement

59SC6A: Installation, Start-up, Operating and Service and Maintenance Instructions
4. Locate assembly through sidewall with rain shield positioned no
more than 1-in. (25 mm) from wall as shown in
5. Disassemble loose pipe fittings. Clean and cement using same
procedures as used for system piping. DO NOT CEMENT
POLYPROPYLENE FITTINGS.
2-Pipe and 1-Pipe Vent Termination
NOTE: Follow the instructions of the vent terminal manufacturer.
These instructions are provided as a reference, only.
!
RECOMMENDED SUPPORT FOR VENT TERMINATIONS
It is recommended that sidewall vent terminations in excess of 24
inches (0.6 M) in vertical length be supported by EITHER the Direct
Vent Termination Kit shown in
or supports fastened to the structure.
Determine an appropriate location for termination kit using the
guidelines provided in section "Locating The Vent Termination" in
this instruction.
1. Cut two holes, one for each pipe, of appropriate size for pipe size
being used.
2. Loosely install elbow in bracket (if used) and place assembly on
combustion-air pipe.
3. Install bracket as shown in
NOTE: For applications using vent pipe option indicated by dashed
lines in
Fig. 40
and
Fig.
41, rotate vent elbow 90_ from position.
Venting System Length Calculations
The Total Equivalent Vent Length (TEVL) for EACH combustion air or vent pipe equals the length of the venting system, plus the equivalent length of
elbows used in the venting system from
Standard vent terminations or factory accessory concentric vent terminations count for zero deduction.
See vent system manufacturer's data for equivalent lengths of flexible vent pipe or other termination systems. DO NOT ASSUME that one foot of
flexible vent pipe equals one foot of straight PVC/ABS DWV vent pipe.
Compare the Total Equivalent Vent Length to the Maximum Equivalent Vent Lengths in
Example 1
A direct-vent 60,000 BTUh furnace installed at 2100 ft. (640M). Venting system includes FOR EACH PIPE:
70 feet (22 M) of vent pipe, 65 feet (20 M) of combustion air inlet pipe, (3) 90º long-radius elbows, (2) 45º long-radius elbows, and a factory accessory
concentric vent kit.
Can this application use 2" (50 mm ND) PVC/ABS DWV vent piping?
Measure the required linear length of air inlet and vent pipe; insert the longest of the two
here
Add equiv length of (3) 90º long-radius elbows
(use the highest number of elbows for either the vent or inlet pipe)
Add equiv length of (2) 45º long-radius elbows
(use the highest number of elbows for either the vent or inlet pipe)
Add equiv length of factory concentric vent term
Add correction for flexible vent pipe, if any
Total Equivalent Vent Length (TEVL)
Maximum Equivalent Vent Length (MEVL)
Is TEVL less than MEVL?
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Fig.
40.
NOTICE
Table 12
or by field-supplied brackets
Fig. 40
and
Fig.
49.
Table
15.
4. Disassemble loose pipe fittings. Clean and cement using same
procedures as used for system piping. DO NOT CEMENT
POLYPROPYLENE FITTINGS.
(Direct Vent / 2-Pipe System ONLY)
When two or more furnaces are vented near each other, two vent
terminations may be installed as shown in
termination, or pair of vent terminations, must be at least 36 in. (914
mm) away from the first two terminations. It is important that vent
terminations be made as shown in
gases.
Inducer Outlet Restrictor
To improve efficiency and operation of 26K, 40K, 60K, 120K, or 140K
BTUh input models on very short vent systems, an inducer outlet
restrictor is required to be installed on the outlet of the inducer assembly.
The outlet restrictor is shown in the footnote of
Equivalent Vent Length. The outlet restrictor for 26K and 40K models is
shipped in the loose parts bag. See
sourcing of 60K, 120K, or 140K inducer outlet restrictors.
To determine if the outlet restrictor is required, see
use an outlet restrictor on the 40K input models when required may
result in flame disturbance or flame sense lockout.
To install the outlet restrictor:
1. Remove the vent elbow from the inducer outlet.
2. Align the lock tabs on the outlet restrictor with the slots on inside
outlet of the inducer assembly.
3. Snap the outlet restrictor in place.
4. Re-install the vent elbow.
5. Torque vent elbow clamp 15-lb-in.
Table
14.
=
70 ft.(22 M)
3
x
3 ft.(0.9 M)
=
9 ft.(2.7 M)
2
x
1.5 ft.(0.5 M)
=
3 ft.(0.9 M)
82 ft.(25 M)
95 ft.(29 M)
47
Fig.
40, but next vent
Fig. 40
to avoid recirculation of vent
Table 14
Table 14
for usage, part numbers and
Table
Use length of the longer of the vent
or air inlet piping system
From
Table 15
From
Table 15
0 ft.
From
Table 15
From Vent Manufacturer's
0 ft.
instructions; zero for PVC/ABS DWV
Add all of the above lines
For 2" pipe from
Table 14
YES
Therefore, 2" pipe MAY be used