Step 4 Then, check that the pressure reading on the pressure gauge remains unchanged.
----End
Follow-up Procedure
●
●
3.5.7 Leakage Test with Water
Context
●
Issue 09 (2022-12-15)
If the pressure decreases, apply soapy water on the pipes, especially pipe
joints to check for any leakage.
If the pressure preservation is good, wrap all pipes and connectors with
thermal insulation foam, and mount bonnets on the needle valves.
To avoid blockage of the heat exchanger in the smart cooling product due to
foreign matter from the main pipe during the construction, you are advised to