Properties
1.1 2/4AI RTD ST analog electronic module (6ES7134-4JB51-0AB0)
Using PTC resistors
PTCs are suitable for temperature monitoring and as thermal protective devices for complex
drives and transformer windings.
● Select "Two-wire resistor" and "PTC" when configuring:
● Connect the PTC in accordance with the two-wire connection method.
● Apply PTC resistors of type A (PTC thermistors) in accordance with DIN / VDE 0660,
● If the diagnosis "Overrun/underrun" is enabled, a diagnosis "Lower limit exceeded"
● Sensor data for the PTC resistor:
Switching points
(TNF-5) °C
(TNF+5) °C
(TNF+15) °C
Measuring circuit
voltage
Voltage on the PTC
12
part 302.
indicating a short-circuit is indicated at resistance values < 18 Ω.
Property
specifications
Behavior with rising temperature
< 550 Ω
550 Ω to 1650 Ω
> 1650 Ω
Behavior with falling temperature
> 750 Ω
750 Ω to 540 Ω
< 540 Ω
max. 550 Ω
min. 1330 Ω
min. 4000 Ω
max. 7.5V
Technical
Normal range:
SIMATIC S7: Bit 0 = "0", bit 2 = "0" (in the PII)
SIMATIC S5: Bit 3 = "0", bit 5 = "0" (in the PAE)
Prewarning range:
SIMATIC S7: Bit 0 = "0", bit 2 = "1" (in the PII)
SIMATIC S5: Bit 3 = "0", bit 5 = "1" (in the PII)
Addressable range:
SIMATIC S7: Bit 0 = "1", bit 2 = "0" (in the PII)
SIMATIC S5: Bit 3 = "1", bit 5 = "0" (in the PII)
Addressable range:
SIMATIC S7: Bit 0 = "1", bit 2 = "0" (in the PII)
SIMATIC S5: Bit 3 = "1", bit 5 = "0" (in the PII)
Prewarning range:
SIMATIC S7: Bit 0 = "0", bit 2 = "1" (in the PII)
SIMATIC S5: Bit 3 = "0", bit 5 = "1" (in the PII)
Normal range:
SIMATIC S7: Bit 0 = "0", bit 2 = "0" (in the PII)
SIMATIC S5: Bit 3 = "0", bit 5 = "0" (in the PII)
TNF= rated operating temperature
2/4AI RTD ST analog electronic module (6ES7134-4JB51-0AB0)