Supported DNP3.0 Objects ....................4 DNP3.0 Analog Input Value Change Events versus PQube 3 Internal Events ....6 Security ..........................6 PQube 3 DNP3.0 Datapoints Group 30 Analog Input Point Map ..................7 Group 12 Binary Output Point Map ................46 Appendix Group 86 Dataset Descriptors Point Map ...............
DNP3.0 Reference Manual 1 Background The PQube 3 supports the Distributed Network Protocol version 3 (DNP3.0) outstation device software module with communication over Ethernet TCP/IP. The PQube 3 supports DNP3.0 level 1-4 functionality with Analog Point Objects, Binary Output Control Objects, Dataset Objects, Octet String Objects, Analog Event Objects, and File Transfer Objects.
DNP3.0 Reference Manual 2 Basic Outstation Configuration and Settings DNP3.0 is enabled and configured with the following Setup.ini file tags in the section “DNP3”: • DNP3/Enable_DNP3 o Enable the DNP3 slave outstation client. Default OFF. • DNP3/DNP3_Port o Configure the DNP3 outstation listening port. Default 20000. •...
Page 5
DNP3.0 Reference Manual Relay 1 operates independently, as it’s not possible to configure the latching functionality of the relay. Instead, relay 1 will always trip on a reboot/power down, and close when the PQube 3 locks onto a frequency and is ready to start measurement. The pulse functionality is presently not supported.
DNP3.0 Reference Manual 2.4 DNP3.0 Analog Input Value Change Events versus PQube 3 Internal Events Events hold two meanings in the DNP3.0/PQube 3 space: • DNP3.0 analog change events are changes in values on Analog Input points creating an unsolicited message upload from the PQube 3 when an analog point exceeds a configured DNP3.0 analog input threshold range.
DNP3.0 Reference Manual 3 PQube 3 DNP3.0 Datapoints 3.1 Group 30 Analog Input Point Map The following DNP3.0 analog input object point map indicates the available PQube 3 meters, which are sampled at 2 Hz with support for format variations 1-5.
DNP3.0 Reference Manual 4 Appendix 4.1 Group 86 Dataset Descriptors Point Map The following DNP3.0 Dataset Descriptors point map indicate the PQube 3 event name, event summary, daily trends, weekly trends, and monthly trends: Point Index: Descriptor Element: Descriptor Name •...
DNP3.0 Reference Manual 4.3 Group 0 Device Attribute Object Point Map The PQube 3 returns the following Group 0 Device Attribute Variations: Variation Index: Device Attribute • 212: Number of master-defined data set prototypes • 213: Number of outstation-defined data set prototypes •...
Need help?
Do you have a question about the PQube 3 DNP3.0 and is the answer not in the manual?
Questions and answers