5) CO2 control
This controller allows controlling level of carbon dioxide (CO2) in a room. Connect 0..10VDC CO2 sensor di-
rectly to the controller and configure the controller. In service mode, in item F.14 set 2, and F.15 and F.16 should
be set based on the sensor specification.
After CO2 sensor is connected and required parameters are set in the service menu, select desired CO2
level (P.05) and allowed difference from the set (P.05) limit in the user menu. If allowed difference is exceeded,
controller will automatically start fans at maximum (4) speed and "CO2" will be shown in digital display. After set
CO2 level (P.05) is reached, controller will return to previous mode.
NOTE: The air quality converters and remote controller (when fan is controlled) must be powered from a
separate power source. It is not supplied with the remote controller.
Service menu
To enter service menu:
1. Go to "Off" state (if controller is on, press down element B1 for 3 seconds).
2. Press down B1 and B2 for 3 seconds.
3. Using elements B4 and B6, enter security code "022" and confirm with element B5.
In the service menu, settings of menu items (F.01, F.02 etc.) are shown sequentially. Menu item is selected
using elements B4 and B6. After pressing B5, value of selected parameter is shown and can be changed using
elements B4 and B6. Pressing B5 saves the parameters and returns to the setting menu.
To exit the service menu, press down element B1 for 3 seconds (controller goes to switch off state).
No.
.
.
.3
.4
.5
.6
.7
.8
.9
.
.
.
.3
.4
42
0...10 VDC
(instead of AHU)
MODBUS
CONTROLLER
(master)
sensor
0...10 VDC
Name Possible values
Fan control
Switch of locking 0: Not locked
Speed 1 (%) 0 – 100
Speed 2 (%) 0 – 100
Speed 3 (%) 0 – 100
Speed 4 (boost) (%) 0 – 100
Speed 1 (Pa) 0 – 999
Speed 2 (Pa) 0 – 999
Speed 3 (Pa) 0 – 999
Speed 4 (boost) (Pa) 0 – 999
Pressure PID – P 0 –999
Pressure PID – I 0 – 999
Pressure PID – D 0 – 999
Converter
FAN
AHU
(slave)
CO2
0: 0..100%
1: Fixed speeds
2: Based on fixed pressures
1: Fan always operates at minimum speed 1
0: No
1: Pressure
2: CO2
Default
value
1
1
20
40
70
100
5
10
25
40
5
10
0
0
www.salda.lt