KLIC-DA LT
KNX/DAIKIN Altherma LT Gateway
ZN1CL-KLIC-DA
Application Program Version: [1.0]
User Manual Version: [1.0]_a
www.zennio.com

Advertisement

Table of Contents
loading

Summary of Contents for Zennio KLIC-DA LT

  • Page 1 KLIC-DA LT KNX/DAIKIN Altherma LT Gateway ZN1CL-KLIC-DA Application Program Version: [1.0] User Manual Version: [1.0]_a www.zennio.com...
  • Page 2: Table Of Contents

    KLIC-DA LT Contents Introduction ........................3 KLIC-DA ........................3 1.1.1 KLIC-DA LT......................4 Installation ........................ 5 Configuration ........................7 Domestic Hot Water Management (DHW) ..............7 Climate control management ..................7 Error Handling ......................7 Additional Indicators....................8 Start-up ........................8 ETS Parameterisation ......................
  • Page 3: Introduction

    KNX domotic environment. As a bidirectional KNX / Altherma interface, KLIC-DA provides full communication between any KNX device (e.g., the InZennio Z41 touch screen from Zennio) and the Altherma system, which can therefore be controlled analogously as from the specific Altherma user interfaces.
  • Page 4: Klic-Da Lt

    Control through a user interface configured as a thermostat, Control though an external thermostat (TH). The KLIC-DA LT application program is only compatible with Altherma LT systems configured for an LWT control, and with only one climate zone (Altherma LT systems permit up to two climate zones with independent setpoint temperatures).
  • Page 5: Installation

    (4) in substitution of the original additional user interface. Once the device is being powered from the KNX bus, both the physical address and the KLIC-DA LT application program can be downloaded. This device does not need any additional external power as it is entirely powered through the KNX bus.
  • Page 6 “At Unit” under “User Interface Location”. For detailed information about the technical features of KLIC-DA, as well as on security and installation procedures, please refer to the device Datasheet, bundled within the original packaging of the device and also available at http://www.zennio.com. http://www.zennio.com Technical Support:...
  • Page 7: Configuration

    KLIC-DA LT 2 CONFIGURATION As stated in section 1.1.1, the KLIC-DA LT application program is only compatible with Altherma LT systems running under an LWT control, and with only one climate zone. The main functionality of KLIC-DA LT is listed next.
  • Page 8: Additional Indicators

    KLIC-DA LT 2.4 ADDITIONAL INDICATORS KLIC-DA LT does monitor other information received from the Altherma LT system, and therefore is able to report it to the KNX bus: Temperatures (an external temperature or that of the DHW tank, the output water flow, the input water flow or of the refrigerant).
  • Page 9 Finally, the KLIC-DA LT application program brings the option to send all the status objects to the KNX bus after a voltage recovery, in order to update other KNX devices.
  • Page 10: Ets Parameterisation

    3 ETS PARAMETERISATION To begin with the parameterisation process of the KLIC-DA interface it is necessary, after launching the ETS program, to import the database of the product (KLIC-DA LT application program). Next, the device should be added to the project. And then, one right-click on the device will permit selecting "Edit parameters", in order to start the configuration.
  • Page 11: Configuration

    KLIC-DA LT 3.1.1 CONFIGURATION In the first place, it is necessary to set the desired Configuration Type, which can be one of the following: Basic, selected by default. This mode permits enabling and making use of the following options:  Domestic Hot Water (DHW), which enables or disables the DHW function.
  • Page 12 Delay will show if the above is set to “Yes”. Regarding the start-up of the device, it is advisable to read section 2.1, as it contains details on how the interaction between KLIC-DA LT and the Altherma LT system starts. http://www.zennio.com Technical Support: http://zennioenglish.zendesk.com...
  • Page 13: Domestic Hot Water

    No additional parameter configuration is required for this function. If enabled, the following communication objects will be available: [DHW] On/Off: one-bit object that will make KLIC-DA LT turn on the DHW function if a “1” is received from the KNX bus, while one “0” will make it turn the function off.
  • Page 14: Climate

    Heating (value “1”). Note: although available from the main user control, the “automatic” mode cannot be activated from KLIC-DA LT. If a mode switch order is received from the KNX bus, KLIC-DA LT will ensure that the automatic mode gets deactivated in the climate system.
  • Page 15: Error Handling

    Note: if two or more additional user controls are found to exist in the P1/P2 bus, KLIC-DA LT will report a communication error and will then require that the Altherma LT system is switched off prior to removing the unneeded additional control.
  • Page 16: Actuators (Status)

    [Temperatures] Refrigerant: two-byte object that reflects the current temperature of the refrigerant, as reported by the Altherma LT system. Whenever the Altherma LT system notifies a temperature change, KLIC-DA LT will automatically send the corresponding object to the KNX bus.
  • Page 17: Additional Information (Status)

    Altherma LT system may use other units), as reported by the Altherma LT system. Whenever the Altherma LT system notifies a change in the status of the above indicators, KLIC-DA LT will automatically send the corresponding object to the KNX bus. http://www.zennio.com Technical Support: http://zennioenglish.zendesk.com...
  • Page 18: Annex I. Communication Objects

    KLIC-DA LT ANNEX I. COMMUNICATION OBJECTS “Functional range” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
  • Page 19 KLIC-DA LT 17 2 Bytes C T R - - DPT_Value_Temp -273.0 - 670760.0 [Temperatures] Outdoor Temperature Current Outdoor Temperature C T R - - 18 2 Bytes DPT_Value_Temp -273.0 - 670760.0 [Temperatures] Leaving Water Current Leaving Water Temperature Current Leaving Water (Plate Heat Exchanger)