Zennio KLIC-DD3 User Manual

Knx - daikin gateway for domestic range daikin a/c units

Advertisement

Quick Links

KLIC-DD3
KNX - Daikin Gateway for
Domestic Range Daikin A/C Units
ZCL-DD3
Application program version: [1.0]
User manual edition: [1.0]_a
www.zennio.com

Advertisement

Table of Contents
loading

Summary of Contents for Zennio KLIC-DD3

  • Page 1  KLIC-DD3 KNX - Daikin Gateway for Domestic Range Daikin A/C Units ZCL-DD3 Application program version: [1.0] User manual edition: [1.0]_a www.zennio.com...
  • Page 2: Table Of Contents

    KLIC-DD3 CONTENTS Contents ............................2 Introduction .......................... 3 1.1 KLIC-DD3 ........................... 3 1.2 Installation ........................4 1.3 Start-Up and Power Loss ....................5 Configuration......................... 6 2.1 General ..........................6 2.2 Inputs ..........................8 2.2.1 Binary Input ......................8 2.2.2 Temperature Probe ....................9 2.2.3...
  • Page 3: Introduction

    KLIC-DD3 1 INTRODUCTION 1.1 KLIC-DD3 KLIC-DD3 from Zennio is a gateway that provides full-duplex communication between the KNX home automation system and domestic range Daikin air-conditioning systems through the S21 port of interior units. Because of this bidirectional communication, the air conditioning system can be controlled from the home automation system in the same manner as it is through its own controls.
  • Page 4: Installation

    Communication cable (4): 5-wire cable with S21 connector that will connect KLIC-DD3 and the A/C unit. The other end of the cable, therefore, is intended to be connected to the S21 connector in the PCB board of the internal unit.
  • Page 5: Start-Up And Power Loss

    Important: Control the A/C unit both through its incorporated wired remote control and through KLIC-DD3 is not possible, due to both of them use the S21 port. By the other hand, if the wireless control is employed, it must be taken into account that orders sent from the wireless control will have a higher priority than those sent through KLIC-DD3.
  • Page 6: Configuration

    Logic functions: see section 2.3. AC gateway: see section 2.4. The latter entails all functions specific to KLIC-DD3, i.e., all the functions related to interfacing with the A/C unit and to the management of the climate control system. ETS PARAMETERISATION...
  • Page 7 KLIC-DD3 explained in later sections of this document. Please note that AC Gateway is permanently enabled. Heartbeat (Periodical Alive Notification): this parameter lets the integrator incorporate a one-bit object to the project (“[Heartbeat] Object to Send ‘1’”) that will be sent periodically with value “1” to notify that the device is still working (still alive).
  • Page 8: Inputs

    All inputs are disabled by default. Depending on the function selected for each input, additional tabs will be included in the menu on the left. 2.2.1 BINARY INPUT Please refer to the “Binary Inputs” user manual, available in the KLIC-DD3 product section, at the Zennio website (www.zennio.com). http://www.zennio.com Technical Support: http://support.zennio.com...
  • Page 9: Temperature Probe

    It is possible to connect motion detectors (models ZN1IO-DETEC-P and ZN1IO- DETEC-X from Zennio) to the input ports of KLIC-DD3. Please refer to the “Motion Detector” user manual, available in the KLIC-DD3 product section, at the Zennio website (www.zennio.com). Notes: The ZN1IO-DETEC-P motion detector is compatible with a variety of Zennio devices.
  • Page 10: Logic Functions

    KNX bus, which can be done every time the function is executed, periodically or only when the result differs from the last one. Please refer to the “Logic Functions” user manual (available in the KLIC-DD3 product section at the Zennio homepage, www.zennio.com) for detailed information about the functionality and the configuration of the related parameters.
  • Page 11: Ac Gateway

    KLIC-DD3 allows controlling and monitoring an air-conditioning unit in the same way it would be through the wired remote control it is provided with. Through the KNX bus, KLIC-DD3 can be sent orders to control the following basic functions of the air conditioning unit: On/Off switch of the air-conditioning unit.
  • Page 12 The Configuration window under AC Gateway provides the following parameters: Figure 6. AC Gateway. Configuration. OPERATION MODES KLIC-DD3 allows controlling the A/C unit operating mode through the following objects, available by default: “[AC] Mode”: 1-Byte object which allows selecting the A/C unit operation mode.
  • Page 13 KLIC-DD3 “[AA] Mode (status)”: 1-Byte objet which allows knowing the A/C unit operating mode status. Object Value A/C unit mode Auto Heating Cooling Fan only Table 1. A/C unit operating modes. Note: In case of having selected humidifying unit, other additional modes will be available.
  • Page 14 VENTILATION The Fan function allows sending the A/C unit orders to switch the ventilation speed along the available levels (5 levels and automatic mode). To that end, KLIC-DD3 provides a percentage control through the objects “[AC] Fan: percentage control” y “[AC] Fan: percentage control (Status)”, available by default.
  • Page 15 KLIC-DD3 Individual object for automatic mode: enables the “[AC] Fan: Automatic” and “[AC] Fan: Automatic (Status)” one-bit objects, which will let activating/deactivating the automatic mode or reading the current status, respectively. Moreover, the polarity can be configured by parameter:  Automatic Mode Object Polarity: sets the polarity of the above objects: “0 = Automatic On;...
  • Page 16 Heating and Auto modes), provided that the limits are still within the predefined limits of the A/C unit. When KLIC-DD3 receives an order to send the A/C unit a setpoint which is greater (or lower) than the configured limits, it will actually send the limit value.
  • Page 17 The A/C unit set a fixed temperature setpoint in Fan and Dry mode, this is the reason why KLIC-DD3 will not send the setpoint value to A/C unit, however the value will be save to send when leaving these modes.
  • Page 18 KLIC-DD3 Once the humidifying unit is enabled in AC Gateway Configuration section, the following objects are available: “[AC] Humidity Adjust: Operation Point (%)”: 1-Byte object to select the desired humidity operation point. Table 4 represents the percentage values that refer to each of the 5 humidity operation points.
  • Page 19 KLIC-DD3 Once Ururu humidification is activated, A/C unit turns on, activates Heating mode and the humidify process starts. Fan speed level will remain and temperature setpoint will not be accessible (in case of modifying temperature setpoint while this mode is running, Ururu humidification mode will be deactivated, and Humid heating operation, that will be explain later, will be activated).
  • Page 20  Automatic Off Object Polarity: sets the polarity of the above object: “0 = Activate; 1 = Deactivate” o “0 = Deactivate; 1 = Activate”.  Automatic Off Delay: sets the time, in seconds, KLIC-DD3 waits before switching the A/C machine off. Any switch-off order received during the delay will abort the time count.
  • Page 21 Initial Configuration: allows setting the desired initial state that KLIC-DD3 will send the A/C unit after programming or restarting the device:  “Default”: the initial state will be the last one KLIC-DD3 is aware of.  “Custom”: see section 2.4.2.
  • Page 22: Initial Configuration

    KLIC-DD3 2.4.2 INITIAL CONFIGURATION The custom initial configuration allows setting the desired status that KLIC-DD3 will send the A/C unit after downloading or restarting the device. This status is defined in terms of on/off, mode, fan speed, flaps position and temperature setpoint.
  • Page 23: Scenes

    2.4.3 SCENES The Scenes function allows defining a set of statuses (in terms of On/Off, mode, fan speed, etc.) that KLIC-DD3 will send to the A/C unit whenever it receives the corresponding scene values from the KNX bus. http://www.zennio.com Technical Support: http://support.zennio.com...
  • Page 24 KLIC-DD3 ETS PARAMETRISATION After enabling this function (see section 2.4.1), a new tab named Scenes will be incorporated to the tab tree. It allows setting up different scenes (up to 5), consisting each of them in a set of orders to be sent to the A/C unit upon the reception, through the KNX bus and by means of the Scenes object, of the corresponding scene value (decreased by 1, according to the KNX standard).
  • Page 25: Error Handling

     Setpoint: “No change” or any value between 10ºC and 32ºC. 2.4.4 ERROR HANDLING KLIC-DD3 is capable of managing two error types: Communication or internal errors: errors in the communication process between KLIC-DD3 and the A/C unit: http://www.zennio.com Technical Support: http://support.zennio.com...
  • Page 26  Wrong acknowledgement: KLIC-DD3 received an unexpected response after sending a request to the A/C unit. Errors in the A/C unit: errors reported by the A/C unit itself. KLIC-DD3 can notify the KNX bus about the reported error code, although referring to the specific documentation of the A/C machine is advisable in order to obtain further information.
  • Page 27 KLIC-DD3  “[AC] A/C unit Error: Active Error”: 1-Bit object which indicate that there is an error in the A/C unit.  “[AC] A/C unit Error: Error Code”: 14-Byte object that supplies the error code. In case the A/C unit reports an error, the former object will be sent with value of “1”, while the latter will report the corresponding error code.
  • Page 28: Annex I. Communication Objects

    KLIC-DD3 ANNEX I. COMMUNICATION OBJECTS “Functional range” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
  • Page 29 KLIC-DD3 0xC (Inc. by 12%) 0xD (Inc. by 6%) 0xE (Inc. by 3%) 0xF (Inc. by 1%) 0x0 (Stop) 0x1 (Dec. by 100%) … 4 Bit C T - - - DPT_Control_Dimming 0x8 (Stop) [Ix] [Short Press] Darker Decrease Brightness 0x9 (Inc.
  • Page 30 KLIC-DD3 (Switched) 0x0 (Stop) 0x1 (Dec. by 100%) … 4 Bit C T - - - DPT_Control_Dimming 0x8 (Stop) [Ix] [Long Press] Brighter Long Pr. -> Brighter; Release -> Stop 0x9 (Inc. by 100%) … 0xF (Inc. by 1%) 0x0 (Stop) 0x1 (Dec.
  • Page 31 KLIC-DD3 1 Byte C - - W - DPT_Scaling 0% - 100% [Ix] [Long Press] Dimming Status (Input) 0% - 100% 19, 25, 31 1 Byte C - - W - DPT_Scaling 0% - 100% [Ix] [Long Press] Shutter Status (Input) 0% = Top;...
  • Page 32 KLIC-DD3 108, 113, 51, 56, 61, 80, 85, 90, 1 Bit C - - W - DPT_Enable [Ix] [Cx] Enable Channel According to parameters 109, 114, 52, 57, 62, 81, 86, 91, 1 Bit C - - W - DPT_Switch [Ix] [Cx] Force State 0 = No Detection;...
  • Page 33 KLIC-DD3 Unable to Access to the Internal Communication 1 Bit C T R - - DPT_Alarm [AC] Internal Error: Communication Port Port 1 Bit C T R - - DPT_Alarm [AC] Internal Error: Timeout No Acknowledgement Received from AC [AC] Internal Error: Wrong...
  • Page 34 KLIC-DD3 [AC] Temperature Setpoint: Upper Limit 2 Bytes C T R - - DPT_Value_Temp -273.00 - 670760.00 [10...32]ºC (Status) [0]% = Off; [0.4...25.1]% = Low; 1 Byte C - - W - DPT_Scaling 0% - 100% [AC] Humidity Adjust: Operation Point (%) [25.5...50.2]% = Standard;...
  • Page 35 Join and send us your inquiries about Zennio devices: http://support.zennio.com Zennio Avance y Tecnología S.L. C/ Río Jarama, 132. Nave P-8.11 45007 Toledo (Spain). Tel. +34 925 232 002. www.zennio.com info@zennio.com...