Prepare Boiler Location - Weil-McLain SVF 500 Manual

Commercial condensing gas-fired water boilers
Hide thumbs Also See for SVF 500:
Table of Contents

Advertisement

svf
series
500/600
This section is intended to provide installation
instructions for qualified heating installers.
Section Contents

Prepare Boiler Location

Installation Compliance Requirements
WARNING
!
Installation and service must be performed
by a qualified installer, service agency, or gas
supplier. Install the equipment in accordance
with this manual to avoid an unsafe operating
condition, which can result in severe personal
injury, death, or substantial property damage.
• Local, state, provincial, and national codes, laws,
regulations, and ordinances
• National Fuel Gas Code - ANSI Z223 1/NFPA 54,
latest edition
• National Electrical Code - ANSI/NFPA 70, latest
edition For Canada, electrical installation and
grounding must be in accordance with Canadian
Electrical Code, Part 1 - CSA C22 1, and local codes
550-100-273/0523
boiler manual
1
SeCTion 2
Installation
7
12
17
26
27
30
35
39
41
44
47
50
52
53
56
59
60
• For Canada only: Natural Gas and Propane
Installation Code - CAN/CSA B149 1, and local codes
• Where required by the authority having
jurisdiction, the installation must conform to the
Standard for Controls and Safety Devices for
Automatically Fired Boilers - ANSI/ASME CSD-1,
latest edition
IMPORTANT
The SVF boiler manifold and controls met safe
lighting and other performance criteria when the boiler
underwent tests specified in ANSI Z21.13, latest edition.
Checks Before Boiler Installation
1
Check for nearby connections to:
• System water piping
• Venting connections
• Gas supply piping
• Electrical Power
• Location of drain for condensate
2
Check area around boiler Remove any
combustible materials, gasoline, and other
flammable liquids.
WARNING
!
Failure to keep boiler area clear and free of
combustible materials, gasoline, and other
flammable liquids and vapors can create an
explosion hazard, which can result in severe
personal injury, death, or substantial property
damage.
3
Check the boiler location to ensure it protects the
gas control system components from dripping
or spraying water and rain during operation or
service
4
If a new boiler is replacing the existing boiler,
check for and correct system problems:
• System leaks causing oxygen corrosion or heat
exchanger cracks from hard water deposits
• Incorrect expansion tank sizing
• Lack of freeze protection in boiler water
insTallaTion
7
1
2
3
4
5
6
7
8