Parameter Setting - Baxi HP40-XX-MB Operation Manual

Wired controller
Table of Contents

Advertisement

132 (PLC:40133)
Unit target frequency
133 (PLC:40134)
Dc bus current
134
(PLC:40135)
Dc bus voltage
135 (PLC:40136)
TF module temperature
Hydraulic module curve T1S
136 (PLC:40137)
calculated value 1
Hydraulic module curve
137 (PLC:40138)
T1S calculated value 2
138 (PLC:40139)
Water flow
Limit scheme of outdoor
139 (PLC:40140)
unit current
140 (PLC:40141)
Ability of Hydraulic module
2)Parameter setting
Registeraddress Description
Home appliance type
200 (PLC:40201)
201 (PLC: 40202)
Temperature upper limit of T1S cooling
202 (PLC: 40203)
Temperature lower limit of T1S cooling
203 (PLC: 40204)
Temperature upper limit of T1S heating
204 (PLC: 40205)
Temperature lower limit of T1S heating
205 (PLC: 40206)
Temperature upper limit of TS setting
206 (PLC: 40207)
Temperature lower limit of TS setting
207 (PLC: 40208)
Temperature upper limit of water heating
208 (PLC: 40209)
Temperature lower limit of water heating
209 (PLC: 40210)
PUMP RUNNING TIME
210 (PLC: 40211)

Parameter setting 1

In A
The actual value/10, in V
Feedback on outdoor unit,in °C
The corresponding calculated value of zone 1
The corresponding calculated value of zone 2
The actual value*100, in m3/H
Scheme value
The actual value*100, in kW
Remarks
The upper 8 bit is the home appliance type:
Central heating: 0x07
DHW PUMP water return running time. It is five minutes by default
and can be adjusted between 5 and 120 min at an interval of 1 min.
BIT15
Enable water heating
BIT14
Supports water tank electric heater TBH(Read-only)
BIT13
Supports disinfection
BIT12
DHW PUMP, 1: supported; 0: not supported
BIT11
Reserved
BIT10
DHW pump supports Pipe Disinfect
BIT9
Enable cooling
BIT8
T1S cooling high/low temperature settings(Read-only)
BIT7
Enable heating
BIT6:
T1S heating high/low temperature settings(Read-only)
BIT5:
Supports T1 sensor
BIT4:
Supports room temperature Sensor Ta
BIT3:
Supports room thermostat
BIT2:
Room thermostat
BIT1:
Dual Room Thermostat, 0: not supported;
1: supported
BIT0:
0: room cooling/heating first, 1: water heating first
27