Baxi HP40-XX-MB Operation Manual page 30

Wired controller
Table of Contents

Advertisement

211 (PLC:40212)
Parameter setting 2
212 (PLC: 40213)
dT5_On
213 (PLC: 40214)
dT1S5
214 (PLC: 40215)
T_Interval_DHW
215 (PLC: 40216)
T4DHWmax
216 (PLC: 40217)
T4DHWmin
217 (PLC: 40218)
t_TBH_delay
218 (PLC: 40219)
dT5_TBH_off
219 (PLC: 40220)
T4_TBH_on
220 (PLC: 40221)
T5s_DI
221 (PLC: 40222)
t_DI_max
222 (PLC: 40223)
t_DI_hightemp
223 (PLC: 40224)
t_interval_C
224 (PLC: 40225)
dT1SC
225 (PLC: 40226)
dTSC
226 (PLC: 40227)
T4cmax
227 (PLC: 40228)
T4cmin
228 (PLC: 40229)
t_interval_H
229 (PLC: 40230)
dT1SH
230 (PLC: 40231)
dTSH
231 (PLC: 40232)
T4hmax
232 (PLC: 40233)
T4hmin
233 (PLC: 40234)
T4_IBH_on
234 (PLC: 40235)
dT1_IBH_on
235 (PLC: 40236)
t_IBH_delay
BIT15
Reserved
BIT14
Reserved
BIT13
Reserved
BIT12
Reserved
BIT11
Reserved
BIT10
Reserved
BIT9
Reserved
BIT8
Define the port,
0=remote ON/OFF; 1=DHW heater
BIT7
Smart grid, 0=NON; 1=YES
BIT6:
Enable or disable the Tw2, 0=NON ; 1=YES
BIT5:
Setting the high/low temperature of cooling mode T1S
BIT4:
Setting the high/low temperature of heating mode T1S
BIT3:
Double zone setting is valid
BIT2:
Reserved
BIT1:
Reserved
BIT0:
Reserved
Default setting: 5°C, range: 2~10°C, setting interval: 1°C
Default setting: 10°C, range: 5~40°C, setting interval: 1°C
Default setting: 5 min, range: 5~30 min, setting interval: 1 min
Default setting: 43°C, range: 35~43°C, setting interval: 1°C
Default setting: -10°C, range: -25~5°C, setting interval: 1°C
Default setting: 30 min, range: 0~240 min, setting interval: 5 min
Default setting: 5°C, range: 0~10°C, setting interval: 1°C
Default setting: 5°C, range: -5~20°C, setting interval: 1°C
Temperature of the disinfection water tank, range: 60~70°C, default
setting: 65°C
Maximum disinfection duration, range: 90~300 min, default setting:
210 min
Disinfection high temperature duration, range: 5~60 min, default setting:
15 min
Time interval of compressor start-up in cooling mode; range: 5~30 min,
default setting: 5 min
Default setting: 5°C, range: 2~10°C, setting interval: 1°C
Default setting: 2°C, range: 1~10°C, setting interval: 1°C
Default setting: 43°C, range: 35~46°C, setting interval: 1°C
Default setting: 10°C, range: -5~25°C, setting interval: 1°C
Time interval of compressor start-up in the heating mode;
range: 5~60 min, default setting: 5 min
Default setting: 5°C, range: 2~10°C, setting interval: 1°C
Default setting: 2°C, range: 1~10°C, setting interval: 1°C
Default setting: 25°C, range: 20~35°C, setting interval: 1°C
Default setting: -15°C, range: -25~5°C, setting interval: 1°C
Ambient temperature for enabling the hydraulic module auxiliary electric
heating IBH, range: -15~10°C; default setting: -5°C
Temperature return difference for enabling the hydraulic module
auxiliary electric heating IBH, range: 2~10°C; default setting: 5°C
Delay time of enabling the hydraulic module auxiliary electric heating
IBH, range: 15~120 min; default setting: 30 min
28