HP StorageWorks HSG60 Installation Instructions Manual page 8

Advertisement

H
2.
For the replacement controller, complete the
following substeps:
H
a. Remove the program card in the replacement
controller, if it is installed.
H
b. Insert the replacement controller (without the
program card installed) into the appropriate
bay, and then engage the controller retaining
levers.
H
c. Press and hold the Reset button, insert the
program card, and continue holding the Reset
button.
H
d. Press and hold the replacement controller Port
#5 button, release the Reset button, and continue
holding the Port #5 button for an additional 5 to
20 seconds (see
Port #5 button after 5 to 20 seconds.
The nonvolatile memory in the replacement
controller is updated, and the controller halts
with an LED code of 33. Port LEDs 1, 2, 5, and
6 are on (see
H
e. Press and release the Reset button.
The replacement controller restarts normally.
H
f. Wait at least 15 seconds after releasing the
Reset button, and then immediately complete
substep
3a. Be sure to wait 15 seconds before
continuing to
Note:
A controller restart can take as long as 60 seconds,
indicated by the temporary cycling of the port LEDs and a flashing
Reset button.
3.
For the operational controller, complete the
following substeps:
a. Press Enter or Return within 3 minutes of
completing
wait 1 minute to allow the replacement
controller to restart.
Note:
If Enter or Return is not pressed within 3 minutes in
3a, the operational controller issues an automated command to
cancel the installation of the replacement controller. This
cancellation causes all the port LEDs on the replacement controller
to go off. If this situation occurs, press Enter to exit
enter the following command from the operational controller:
RESTART OTHER_CONTROLLER
b. Verify that the status of the cache of the
operational controller is good by entering the
following command:
SHOW THIS_CONTROLLER
Figure 5
on page 3). Release the
Figure 5
on page 3).
substep
3a.
substep 2f
to exit FRUTIL, and then
FRUTIL,
H
4.
H
H
H
H
H
H
H
H
substep
H
H
and then
Page 8
c. Complete one of the following steps from the
operational controller:
If the controller reported that the cache and
mirrored cache (if enabled) is good in
substep
3b, proceed to
If the controller reported that the cache and
mirrored cache (if enabled) is not good in
substep
3b, refer to Table 14 through Table
16 in the "Controller and Cache
Replacement Troubleshooting" appendix of
the HP StorageWorks HSG60 and HSG80
Array Controller and Array Controller
Software Maintenance and Service Guide
and take corrective actions.
d. Disconnect the PC or terminal from the
maintenance port of the operational controller.
For the replacement controller, complete the
following substeps:
a. Connect a PC or terminal to the maintenance
port of the replacement controller.
b. Perform the following:
i.
Set the terminal baud rate to 9600.
ii. Press Enter or Return several times to get a
prompt.
iii. Proceed to the next substep.
c. Perform the following verifications:
Verify that the controller restarts in the
following reset configuration by entering the
following command:
SHOW THIS_CONTROLLER
Verify that the controller prompt displays
HSG>.
Verify that the NODE_ID is
0000-0000-0000-0000.
Verify that mirrored cache matches the
original configuration.
Verify that the controller cache is good.
Refer to Table 14 through Table 16 in the
"Controller and Cache Replacement
Troubleshooting" appendix of the HP
StorageWorks HSG60 and HSG80 Array
Controller and Array Controller Software
Maintenance and Service Guide if the cache
is not good.
substep
3d.