SYSTEM SPECIFICATIONS
System Capacity
• Intelligent Signaling Line Circuits (Digital Comm. Loops).............. 1
• Addressable device capacity ....................................................... 50
• Programmable software zones.................................................... 50
• Annunciators................................................................................ 16
Electrical Specifications
AC Power: Operates in either 120 or 240 VAC, 50/60 Hz, 3.25 A,
auto-sensing- no switch required. Wire size: minimum 14 AWG (2.00
mm2) with 600 V insulation. Non-power-limited, supervised.
Battery: Two 12 V 18 AH lead-acid batteries. Battery Charger Capac-
ity: 7-18 AH (ES-50X cabinet holds maximum of two 18 AH batteries.)
Communication Loop: Supervised and power-limited.
Notification Appliance Circuits: Terminal Block provides connec-
tions for two NACs, Class B or Class A. Special Application power.
Power-limited, supervised circuitry. Maximum signaling current per cir-
cuit: 2.5 amps special application, 250mA regulated. End-of-Line
Resistor: 4.7k ohm, ½ watt (P/N 71252 UL listed) for Class B NAC;
system capable of 1.9 kΩ - 22 kΩ ELR range. Refer to the Fire•Lite
Device Compatibility Document for listed compatible devices.
Two Programmable Relays and One Fixed Trouble Relay: Con-
tact rating: 2.0 A @ 30 VDC (resistive), 0.5 A @ 30 VAC (resistive).
Form-C relays, non-power-limited, non-supervised.
Cabinet Specifications
Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.72" (1.82
cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65" (42.29 cm.)
wide x 5.25" (13.34 cm.) deep. Trim Ring (TR-CE): 22.00" (55.88 cm.)
high x 19.65" (49.91 cm.) wide.
Shipping Specifications
Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00" (50.80 cm.) high x
22.5" (57.15 cm.) wide x 8.5" (21.59 cm.) deep.
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 – 49°C/32 –
120°F and at a relative humidity 93% ± 2% RH (noncondensing) at
32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's
standby batteries and the electronic components may be adversely
affected by extreme temperature ranges and humidity. Therefore, it is
recommended that this system and its peripherals be installed in an
environment with a normal room temperature of 15 – 27°C/60 – 80°F.
Page 4 of 4 — DF-60953:D • 3/27/2023
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX:(877) 699-4105.
NFPA Standards
The ES-50X complies with the following NFPA 72 Fire Alarm Systems
requirements:
– LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervi-
sory).
– AUXILIARY (Automatic, Manual and Waterflow) (requires
4XTMF).
– REMOTE STATION (Automatic, Manual and Waterflow) (Where a
DACT is not accepted, the alarm, trouble and supervisory relays
may be connected to UL 864 listed transmitters. For reverse
polarity signaling of alarm and trouble, 4XTMF is required.)
– PROPRIETARY (Automatic, Manual and Waterflow).
– CENTRAL STATION (Automatic, Manual and Waterflow, and
Sprinkler Supervised).
– OT, PSDN (Other Technologies, Packet-switched Data Network)
– IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic).
– CBC 2007 (Seismic)
Agency Listings and Approvals
The listings and approvals below apply to the basic ES-50X control
panel. In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult Fire•Lite for
latest listing status.
ES-50X, ES-50XC, ES-50XI
• UL: S624
• FM approved
• CSFM: 7165-0075:0500, 7165-0075:0511
• FDNY: COA #2021-TMCOAP-009618-AMD
ES-50XP
• ETL: 5017286
• CSFM: 7165-0075:0511
InnovairFlex™ and LiteSpeed™ are trademarks and AlarmNet®, Fire-Lite®
Alarms, SWIFT®, and System Sensor® are registered trademarks of Honeywell
International Inc. AT&T® is a registered trademark of the AT&T Properties,
L.P.Verizon® is a registered trademark of Verizon Trademark Services LLC.
Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
©2023 by Honeywell International Inc. All rights reserved. Unauthorized use of this
document is strictly prohibited.
www.firelite.com
Country of Origin: USA

Advertisement

loading