Parameter
Parameter text
p840[0]
BI: ON / OFF (OFF1)
p1000[0]
Speed setpoint selection
Note: Fixed Frequency setpoints are cumulative, so ensure external relay logic energizes one input at a time. The ESM
overrides this rule and runs to the setpoint defined in P1015.
p1001[0]
CO: Fixed speed setpoint 1
p1002[0]
CO: Fixed speed setpoint 2
p1003[0]
CO: Fixed speed setpoint 3
p1004[0]
CO: Fixed speed setpoint 4
p1015[0]
CO: Fixed speed setpoint 15
p1020[0]
BI: Fixed speed setpoint selection Bit 0
p1021[0]
BI: Fixed speed setpoint selection Bit 1
p1022[0]
BI: Fixed speed setpoint selection Bit 2
p1023[0]
BI: Fixed speed setpoint selection Bit 3
p1113[0]
BI: Setpoint inversion
p1210
Automatic restart, mode
p2103[0]
BI: 1. Acknowledge faults
p3880
BI: ESM activation
p3881
ESM setp source
Note: The following read-only parameters are shown as handy points of interest. Do not try to program these into your drive.
r722
CO/BO: CU digital inputs, status
r1024
CO: Fixed speed setpoint effective
Page 31 of 50
Parameter Value
Control_Unit : r1025.0
[3] Fixed speed setpoint
500
750
1000
1250
1500
Control_Unit : r722.0
Control_Unit : r722.1
Control_Unit : r722.2
Control_Unit : r722.3
0
[26] Acknowledging all faults and reclosing for an ON
command
0
Control_Unit : r722.4
[1] Fixed speed setpoint 15 (p1015)
0000_0000_0000_0000_0000_1000_0000_0000B
0
Building Technologies
Unit
rpm
rpm
rpm
rpm
rpm
rpm
Last Revised: 4/11/2011