This document includes references to SunPower E‐Series, X‐Series, P‐Series, A‐
Series,  M‐Series,  MAX2,  MAX3  and  NE  modules.  These  modules  do  not  have 
grounding  restrictions  and  all  are  compatible  with  high‐efficiency 
transformerless inverters. 
Contents of this manual are subject to change without notice.  
For the latest US & Canada manual please refer to www.sunpower.com/PVInstallGuideUS 
For the latest US & Canada technical specifications please refer to 
www.sunpower.com/PVResidentialSTS (for residential modules)  
www.sunpower.com/PVCommericalSTS (for commercial and utility modules)  
Safety and Installation Instructions  
United States and Canada  
This document applies to all SunPower modules  
listed in Table 1.  
SunPower Corporation 
www.sunpower.com 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Document 001‐14158 Rev AI 
P/N 100345 
P/N 518350 
 

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the E Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SunPower E Series

  • Page 1               Safety and Installation Instructions     United States and Canada     This document applies to all SunPower modules   listed in Table 1.       This document includes references to SunPower E‐Series, X‐Series, P‐Series, A‐   Series,  M‐Series,  MAX2,  MAX3  and  NE  modules.  These  modules  do  not  have  grounding  restrictions  and  all  are  compatible  with  high‐efficiency    transformerless inverters.   ...
  • Page 2: Safety And Installation Instructions

     Do not place anything on the modules, even for a moment because resulting  (United States and Canada)  residue may damage or stain the glass surface.   If the front glass is broken, or the backsheet is torn, contact with any module  1.0 Introduction    surface or module frame can cause electric shock.   Broken J‐boxes or connectors are electrical hazards as well as laceration  These instructions provide safety and installation instructions for UL  hazards. Installers should remove any such module from the array and  Listed SunPower photovoltaic (PV) modules that have the UL logo on the  contact SunPower for disposal instructions.    product label:   Do not install or handle the modules when they are wet or during periods of  high wind.   Do not block drain holes or allow water to pool in or near module frames.     SunPower recommends a conservative minimum cable bend radius of equal         to or greater than 40 mm (1.5”).    IMPORTANT!  Please read these instructions in their entirety before   Unconnected connectors must always be protected from pollution (e.g dust,  installing, wiring, or using this product in any way. Failure to comply  humidity, foreign particles, etc), prior to installation. Do not leave  unconnected (unprotected) connectors exposed to the environment. A clean  with these instructions will invalidate the SunPower Limited  assembly environment is therefore essential to avoid performance  Warranty for PV Modules.    degradation.  1.1 Disclaimer of Liability ...
  • Page 3   SUNPOWER CORPORATION      Safety and Installation Instructions ‐ Document 001‐14158 Rev AI    Table 1: Electrical Characteristics   Current at  Short  Maximum  Voltage at  Open  Voltage at  Open Circuit  Current at  Short Circuit  Maximum  Rated  Rated  Circuit  System  Rated  Rated  Circuit  Module Rated Power  Voltage  Voc  Module Rated Power,  Current, Isc  System Voltage  Power (W) Power,  Current, Isc  Voltage UL  Power (W) Power  Voltage   Vmpp (V) Impp (A) Vmax (V) Impp (A)
  • Page 4: Equipment Grounding

      SUNPOWER CORPORATION      Safety and Installation Instructions ‐ Document 001‐14158 Rev AI    and nut). Use an external‐tooth star washer between the lug and the  Voltage  Open  Short  Rated  Current  Current  Voltage  Power  module frame in order to pierce the anodizing and establish electrical  at Rated  Circuit  Circuit  System  Power  at Rated  Temp.  Temp.  Temp.  Module Power  Voltage   Current,  Safety  contact with the aluminum frame. The assembly must end with a nut that’s  Power,  Coeff. Coeff. Coeff. Vmpp  Voc (V) Isc (A) Class +5/‐0% Impp (A) %/°C %/°C...
  • Page 5   SUNPOWER CORPORATION      Safety and Installation Instructions ‐ Document 001‐14158 Rev AI    Table 2: Module Grounding Key  Module Model Grounding Key   SunPower A‐Series, M‐Series, P‐Series, E‐Series,  Legacy modules must be  X‐Series, MAX2, MAX3 and NE modules have no  positively grounded:  grounding restrictions:  All model numbers  starting with “SPR‐AZZZ”,  “SPR‐AZZZ‐BLK”, “SPR‐ SPR‐ZZZE‐WHT‐D  MZZZ”, “SPR‐MZZZ‐BLK”,  SPR‐ZZZNE‐BLK‐D  SPR‐ZZZ‐WHT‐D  “SPR‐PYY, SPR‐PY‐XXX‐ SPR‐ZZZNE‐WHT‐D  SPR‐ZZZE‐BLK‐D  Configurations 1 and 3 show mounting with rail support, 2 and 4 show mounting  UPP”, “SPR‐EYY”, “SPR‐ SPR‐ZZZ‐BLK‐D  without rail support.  XYY”, “SPR‐MAX2”, or    “SPR‐MAX3”.  For 96 cells, A‐Series, M‐Series and 104c:   IMPORTANT! For optimal performance, SunPower modules listed above  as needing positive grounding must be configured as described. Failure to  comply with this requirement will reduce system performance and  invalidate SunPower’s Limited Power Warranty for PV Modules.    4.3 NEC 2017 690.12 Compliance  Modules containing ‐MLSD in the product name come with a pre‐installed  SunSpec compliant rapid shutdown receiver from Tigo Energy Inc that, when used  and installed with approved equipment, constitute a UL1741 listed array meeting ...
  • Page 6   SUNPOWER CORPORATION      Safety and Installation Instructions ‐ Document 001‐14158 Rev AI        Table 3.1: Mounting Zone Load Ratings for Racking system without rail  Figure 1.a. Module Mounting with rail support for P5 UPP  support (units in Pa)  Module  Downward (+) / Upward (‐) Pressure (Pa) (1)  Configuration  Test/  End Mount  B  C  Module  Frame    Design Load  A  (1&2&3&4) (1&2&3&4)  size  type    (2)  (1&2&3&4)   Test Load  3600/‐3600  8100/‐3600  3600/‐3600  96 cells  G3  Design Load  2400*/‐2400  5400/‐2400  2400/‐2400  Test Load ...
  • Page 7: Mounting Configurations

      SUNPOWER CORPORATION      Safety and Installation Instructions ‐ Document 001‐14158 Rev AI    Helix™ Mounting System: See UL2703 Helix system installation manual for  5.2 Mounting Configurations  details.  Modules integrated into or mounted over a roofing system must be mounted  SunPower‐specified or SunPower‐supplied mounting systems: Mount  over a fire‐resistant roof covering rated for the application. Modules may be  modules with strict adherence to SunPower documentation, using  mounted at any angle, from horizontal to vertical. To reduce soiling, modules  hardware systems supplied by or specified by SunPower.  should be mounted at a minimum of 10 degrees.      Residential (black) module frames have two profile types, G3 and G5. Commercial  5.3 Bifacial Gain  (silver) module frames have permanently attached stacking pins. Mounting  Various environmental and installation parameters affect bifacial gain. Albedo is a  system hardware used with commercial modules must account for the presence  measure of the amount of light reflected from the ground surface. A higher  of these stacking pins. Mechanical specifications for modules are shown in Table  albedo factor will increase irradiance on the backside and result in higher bifacial  4.   gain of the module. The surface conditions, month of the year, time of day, GHI    and DNI both influence the amount of incident rearside irradiance.  In order to prevent water from entering the junction box, which could present a     safety hazard, modules should be oriented with the junction box in the  SunPower recommends to check with solar module mounting hardware supplier  uppermost position and not be mounted such that the cell faces downward (e.g.  in order to determine the Structure Shading factor of your particular installation.  on a tracking structure that positions the modules with the junction box facing  The Structure Shading Factor varies with racking system design, irradiance,  skyward during sleep mode).   albedo and height of module installation above ground and has an overall impact    on the rear side irradiance mismatch. ...
  • Page 8   SUNPOWER CORPORATION      Safety and Installation Instructions ‐ Document 001‐14158 Rev AI    soft sponge or seamless cloth to wipe the glass surface in a circular motion. For    large systems, wet the modules with the cleaning solution, let them stand for five    minutes, and then rinse them with high‐pressure water or a soft squeegee. Do    not use harsh industrial‐strength cleaning materials such as scouring powder,  steel wool, scrapers, blades, or other sharp instruments to clean the module  glass. Use of such materials will void the product warranty   Figure 2: Carport Assembly        Table 4: Module Frame Details   Platform Module mounting and ground hole detail       RESIDENTIAL G5 FRAME ONLY (INVISIMOUNT  RESIDENTIAL G3 FRAME ONLY   COMPATIBLE FRAME)   96‐CELL MODULE FRAME DETAIL  96‐CELL MODULE (NO MOUNTING HOLES)  Residential  Modules      SIDE FRAME PROFILE  END FRAME PROFILE  SIDE FRAME PROFILE  END FRAME PROFILE ...
  • Page 9   SUNPOWER CORPORATION      Safety and Installation Instructions ‐ Document 001‐14158 Rev AI    Platform  Module mounting and ground hole detail    FOR COMMERCIAL (SILVER FRAME) MODULES ONLY, INCLUDES STACKING PINS     96‐CELL COMMERCIAL MODULE 128‐CELL COMMERCIAL MODULE 1046 mm [41.2in] 1046 mm [41.2in] 4X Ø4.8 mm [.19in] 1002 mm [39.4in] 4X Ø4.8 mm [0.19in] 1002 mm [39.4in] Drain Holes Drain Holes 4X Ø4.2 mm [.17in] 12X Ø6.6 mm [0.26in]...
  • Page 10 WARNING • Solar module has full voltage even in very low light. • Installation should only be done by a qualified technician. 527040 Patented as shown at www.sunpower.com/patents www.sunpower.com 4X 5.0mm (W) x 15.0mm (L) SLOT 4X 5.0mm (W) x 15.0mm (L) SLOT 20X Ø...
  • Page 11   SUNPOWER CORPORATION      Safety and Installation Instructions ‐ Document 001‐14158 Rev AI    Platform  Module mounting and ground hole detail   FOR A‐SERIES MODULES   Gen 4.2 FRAME MODULE (72‐CELL)  Gen 5.1 FRAME MODULE (72‐CELL)  1999 78.7 1935 76.2 1423 56.0 1200 47.2 1058 41.7 539 21.2 400 15.7 Commercial  Modules  5x15 [0.2x0.6] 4x Ø4.22 (GND) 20x Ø6.8 [.27] SLOTS MOUNTING HOLES    ...
  • Page 12   SUNPOWER CORPORATION      Safety and Installation Instructions ‐ Document 001‐14158 Rev AI    Platform  Module mounting and ground hole detail     FOR  GEN 4.2 MODULES (104‐CELL) 1690 mm 1500 mm 1300 mm 1100 mm Residential/  Commercial  Modules  4x Ø 4.2 mm 8x Ø 6.8 mm   Ground Holes Mounting Holes   SIDE FRAME PROFILE  END FRAME PROFILE 24 mm 32 mm  ...
  • Page 13   SUNPOWER CORPORATION      Safety and Installation Instructions ‐ Document 001‐14158 Rev AI    Platform  Module mounting and ground hole detail     FOR  GEN 4.3 MODULES (P5 UPP) 2384 mm [93.86in] 1400 mm[55.12in] 1100 mm [43.31in] 400 mm [15.75in] Commercial  Modules  4X 10mm [0.39in] (L) 8X 14mm [0.55in] (L) 4X Ø4.2mm [0.17in] x 7mm [0.27in] (W) x 9mm [0.35in] (W) Ground Holes R3.5mm [0.14in]...

This manual is also suitable for:

X seriesP seriesA seriesM seriesMax2Max3