Daikin DC97MC Installation Instructions Manual

Daikin DC97MC Installation Instructions Manual

Modulating gas furnace
Table of Contents

Advertisement

DM97MC & DC97MC
M
ODULATING
(Type FSP CATEGORY IV Direct
or Non Direct Vent Air Furnace)
These furnaces comply with requirements em-
bodied in the American National Standard / Na-
tional Standard of Canada ANSI Z21.47·CSA-2.3
Gas Fired Central Furnaces.
s a professional installer you have an obligation to know
A
the product better than the customer. This includes all
safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself
with this Instruction Manual. Pay special attention to all
safety warnings. Often during installation or repair it is
possible to place yourself in a position which is more
hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product
safely and to know it well enough to be able to instruct a
customer in its safe use.
Safety is a matter of common sense...a matter of thinking
before acting. Most dealers have a list of specific good
safety practices...follow them.
The precautions listed in this Installation Manual are
intended as supplemental to existing practices. However,
if there is a direct conflict between existing practices
and the content of this manual, the precautions listed
here take precedence.
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION.
NOTE: Please contact your distributor or our website for
*
the applicable Specification Sheet referred to in this manual.
IOD-2007F
2/2017
G
F
AS
URNACE
Installer:
Affix all manuals
adjacent to the unit.
Our continuing commitment to quality products may mean a change in specifications without notice.
© 2014-2017
5151 San Felipe St., Suite 500, Houston, TX 77056
www.daikincomfort.com
INSTALLATION INSTRUCTIONS

TABLE OF CONTENTS

S
AFETY
.......................................... 4
E
D
LECTROSTATIC
ISCHARGE
........................................... 5
PRODUCT DESCRIPTION ....................................... 5
.................................................... 5
PRODUCT APPLICATION ....................................... 6
C
A
E
F
R
....................................... 9
T
L
............................................ 9
C
& V
I
P
............................................. 12
H
A
& C
F
S
............................................ 13
F
C
P
S
D
T
L
.......................................... 13
RAIN
L
........................................................ 13
A
E
G
D
...................................................... 14
RAIN
F
P
............................................. 14
P
G
/H
A
I
V
/F
& C
ENT
D
: N
-D
UAL
ON
M
P
V
/F
ROPER
ENT
LUE AND
T
L
........................................ 16
C
V
ENT
S
F
C
C
A
P
........................................... 18
V
/I
T
F
ENT
NTAKE
ERMINATIONS
V
............................................ 21
URNACES
C
V
T
S
V
............................................ 22
IDE
ENT
C
D
L
& D
G
D
I
F
........................................... 22
IELD
U
M
I
V
D
....................................... 23
RAIN
D
........................................ 23
RAIN
U
M
I
H
PFLOW
ODEL
NSTALLED
U
M
I
H
PFLOW
ODEL
NSTALLED
U
M
I
H
PFLOW
ODEL
NSTALLED
W
L
S
D
- A
ITH
EFT
IDE
OWN
C
OUNTERFLOW
D
........................................ 25
RAIN
D
E
R
S
....................................... 26
RAIN
XITING
IGHT
IDE
..................................... 3
(ESD) P
.............. 4
.................................... 8
........................ 9
......................... 13
T
L
................ 13
L
C
............. 14
.......................... 14
A
P
........................... 14
/D
V
................ 14
IRECT
IRECT
............................... 15
A
IR
A
IR
............................... 18
I
M
OR
NSTALLATION OF
ULTIPLE
................................. 22
T
............................. 22
................................... 22
.......................... 23
R
S
ORIZONTALLY WITH
IGHT
IDE
ORIZONTALLY WITH
ORIZONTALLY
.......................... 25
LTERNATE
V
.................... 25
.... 15
... 16
D
IRECT
D
24
OWN
24

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DC97MC and is the answer not in the manual?

Questions and answers

Summary of Contents for Daikin DC97MC

  • Page 1: Table Of Contents

    INSTALLATION INSTRUCTIONS DM97MC & DC97MC TABLE OF CONTENTS ........3 AFETY ONSIDERATIONS ODULATING URNACE .......... 4 HIPPING NSPECTION (ESD) P ....4 LECTROSTATIC ISCHARGE RECAUTIONS ........... 5 NSTALLER (Type FSP CATEGORY IV Direct PRODUCT DESCRIPTION ........5 ............ 5 or Non Direct Vent Air Furnace) EATURES PRODUCT APPLICATION ........
  • Page 2 TABLE OF CONTENTS ....26 ..........49 OUNTERFLOW ODEL NSTALLED ERTICALLY AULT ECALL EQUENCE : ..........49 ........26 AULT LEAR EQUENCE RAIN XITING NORMAL SEQUENCE OF OPERATION ......49 ........26 RAIN XITING IGHT ............... 49 OWER OUNTERFLOW ODEL NSTALLED ORIZONTALLY WITH IGHT...
  • Page 3: Considerations

    AFETY ONSIDERATIONS WARNING Adhere to the following warnings and cautions when install- O PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER ing, adjusting, altering, servicing, or operating the furnace. INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE To ensure proper installation and operation, thoroughly read REFER TO THIS MANUAL OR ADDITIONAL ASSISTANCE OR this manual for specifics pertaining to the installation and...
  • Page 4: Shipping Inspection

    RISQUE D'EMPOISONNEMENT AU MONOXYDE DE CARBONE Advertencia especial para la instalación de calentadores ó manejadoras de aire en áreas cerradas como estacionamientos ó cuartos de servicio. Cette ventilation est nécessaire pour éviter le danger d'intoxication Las emisiones de monóxido de carbono pueden circular a través au CO pouvant survenir si un appareil produisant du monoxyde del aparato cuando se opera en cualquier modo.
  • Page 5: Product Description

    3. Service integrated control module or connecting wiring following the discharge process in step 2. Use caution not to recharge your body with static electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded objects, etc.). If you come in contact with an ungrounded object, repeat step 2 before touching control or wires.
  • Page 6: Product Application

    Gas Valve This product is dual certified. Dual certification means that Gas Line Entrance (Alternate) the combustion air inlet pipe is OPTIONAL and the furnace can Pressure Switch(es) be vented as a: Gas Manifold Non-direct vent (single pipe) central forced air furnace Combustion Air Intake Connection in which combustion air is taken from the installation Hot Surface Igniter...
  • Page 7: Location Requirements & Consideratinos

    • A T-handle gas cock must be used. • Centrally locate the furnace with respect to the proposed or existing air distribution system. • If the unit is to be installed in an attic, the passageway to and the service area around the unit must have •...
  • Page 8: Learances And Ccessibility

    • Counterflow Installation over a combustible floor. deicing salts or chemicals carbon tetrachloride If installation over a combustible floor becomes necessary, use an accessory subbase (see halogen type refrigerants Specification Sheet applicable for your model for cleaning solutions (such as perchloroethylene) details.) A special accessory subbase must be used printing inks for upright counterflow unit installations over any...
  • Page 9: Xisting Urnace Emoval

    54 and/or National Gas and Propane Installation Code CSA B149.1-15. T O P T O P 9. After it has been determined that each appliance con- nected to the venting system properly vents when S ID E S ID E S ID E tested as outlined above, return doors, windows, ex- haust fans, fireplace dampers and any other gas burn-...
  • Page 10 the same space with other gas appliances, such as a water 21 ft Required Volume > ________ _________ other heater, ensure there is an adequate supply of combustion other 1000 Btu/hr and ventilation air for the other appliances. Refer to the latest edition of the National Fuel Gas Code NFPA 54/ANSI (2) For fan-assisted appliances, calculate using the following equation: Z223.1 or CAN/CSA B149.1-15 Installation Codes or appli-...
  • Page 11 within 12 in. (300 mm) of the bottom, of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors, as follows: (1)* Where directly communicating with the outdoors or where communi- cating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in.
  • Page 12: Nstallation Ositions

    (3) Outdoor Opening(s) Size. The outdoor opening(s) size shall be calcu- 9.3.8.2 Ducts shall terminate in an unobstructed space, allowing free move- lated in accordance with the following: ment of combustion air to the appliances. (a) The ratio of the interior spaces shall be the available volume of all communicating spaces divided by the required volume.
  • Page 13: Orizontal Pplications Onsiderations

    2" 2" 3/8" ANGLE IRON PLACES Figure 4A Figure 5 RONT OVER RESSURE WITCH OCATION When a furnace is installed horizontally with left side down, the front cover pressure switch tube must be re-located to the lower port of the collector box cover. 1.
  • Page 14: Lternate Lectrical And As Ine

    & C LTERNATE LECTRICAL AND ONNECTIONS OMBUSTION This furnace has provisions allowing for electrical and gas This manual will refer to the pipe that discharges products line connections through either side panel. In horizontal ap- of combustion to the outdoors as the “vent” pipe or “flue” plications the connections can be made either through the pipe.
  • Page 15: Aterials And Joining Methods

    ROPER LUE AND OMBUSTION IPING RACTICES WARNING Adhere to these instructions to ensure safe and proper furnace O AVOID BODILY INJURY FIRE OR EXPLOSION SOLVENT CEMENTS performance. The length, diameter, and number of elbows of the MUST BE KEPT AWAY FROM ALL IGNITION SOURCES SPARKS OPEN vent/flue pipe and combustion air pipe (when applicable) affects...
  • Page 16: Combustion

    • The combustion air intake termination of a direct vent application should not terminate in an area which is frequently dusty or dirty. NO TRANSITION ON HORIZONTAL PLANE, NOTE: In Canada, the current edition of CAN/CSA B149.1- THIS CREATES A 15 takes precedence over the preceding termination WATER TRAP AND restriction.
  • Page 17 DIRECT VENT TERMINAL CLEARANCES Canadian Installations U.S. Installations Canadian Installations U.S. Installations Clearance to service 3 ft. (91 cm). A= Clearance above grade, 12 in. (30 cm) 12 in. (30 cm) regulator vent outlet. veranda, porch, deck or balcony. (See 1.24.6-i(9)b.) J= Clearance to nonmechanical air 6 in.
  • Page 18: Combustion

    bustion air intake pipe to the air intake coupling using the rubber TANDARD URNACE ONNECTIONS coupling and worm gear hose clamps provided with the unit. The It is the responsibility of the installer to ensure that the piping counterflow rubber coupling allows service removal of air intake connections to the furnace are secure, airtight, and adequately piping internal to the furnace blower compartment.
  • Page 19 Insert flange. Cut 2 ½” long. R 000142 Vent/Flue Pipe Cuts Figure 11 1. Remove screws from vent flange. 2. Remove internal elbow and vent pipe. 3. Cut pipe 2 1/2” from flange. Figure 10 4. Remove cabinet plug adjacent to inducer outlet and install an original cabinet vent hole.
  • Page 20: Ventf

    3) Tee used in the vent/flue termination must be included when deter- LTERNATE OMBUSTION ROVISION mining the number of elbows in the piping system. (Upflow / Horizontal models only) 4) 2 1/2” or 3” diameter pipe can be used in place of 2” diameter pipe. When using the alternate venting location, either in a horizontal left side down installation or a vertical instal- 5) Increased Clearance Configurations using (2) 45 deg.
  • Page 21 12" MIN. VENT/FLUE TEE ( OPTIONAL) 90° 45° ELBOW ELBOWS TURNED DOWN or 90° ELBOW TURNED DOWN 3” - 24” 12" MIN. ABOVE HIGHEST ANTICIPATED SNOW LEVEL Horizontal Termination (Single Pipe) 12" MIN. ABOVE Above Highest Anticipated Snow Level HIGHEST ANTICIPATED SNOW LEV EL Figure 15 &...
  • Page 22: Oncentric Ent Ermination

    • The drain trap must be primed at time of installation. • The drain line between furnace and drain location must meet local and nation codes. 3”MIN • The drain line between furnace and drain location 24”MAX must maintain a 1/4 inch per foot downward slope toward the drain.
  • Page 23: Pflow Odel Nstalled Ertically

    Hose #1 Hose #2 45 degree 45 degree barb-pipe barb-pipe adapter adapter Coupling Installer selects right or left side drain and installs this hose accordingly. Figure 23 100 Degree Elbow RAIN XITING IGHT Figure 21 1. Locate and Install the 45º pipe / hose drain coupling NOTE: Drain components shown from the outside of the cabinet (barbed end goes in for information purposes only.
  • Page 24: Left Side Down

    PFLOW ODEL NSTALLED ORIZONTALLY WITH IGHT PFLOW ODEL NSTALLED ORIZONTALLY WITH Minimum 5 1/2" clearance is required for the drain trap Minimum 5 1/2" clearance is required for the drain trap beneath the furnace. beneath the furnace. *Also see Front Cover Pressure Switch Tube Location on page Hose #2 Hose #11 Hose #6...
  • Page 25: Model Installed Vertically Exiting Left Side

    12. Install the non-grommet end of hose #11 from outside 7. Locate hose #6. Using red clamps, connect between the cabinet in the upper drain hole. Install on collector the coupling and 100 degree elbow, cutting off excess box and secure with a silver clamp. tubing.
  • Page 26: Drain Exiting Left Side

    RAIN XITING IGHT RAIN XITING 1. Install a field supplied rubber coupling secured with a 1 1/4” clamp to enable removing the trap for future cleaning. Alternately, a PVC fitting may be glued on the trap outlet. 2. Install drain per local and National codes. RAIN XITING IGHT...
  • Page 27: Minimum 5 1/2" Clearance Is Required For The Drain Trap Beneath The Furnace

    1. Remove the drain trap and factory installed drain tube 4. Place radius end of hose #4 (factory installed) on the assemblies. collector box drain port and secure with a silver clamp. 2. Remove two 1’’ plugs from right side of cabinet. 5.
  • Page 28: Wiring Harness

    UNCTION ELOCATION CAUTION ABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING WARNING CONTROLS IRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS DGES OF SHEET METAL HOLES MAY BE SHARP SE GLOVES AS A OPERATION ERIFY PROPER OPERATION AFTER SERVICING PRECAUTION WHEN REMOVING HOLE PLUGS IRING ARNESS WARNING...
  • Page 29: Volt Thermostat Wiring

    24 V HERMOSTAT IRING IRE ROUTING MUST NOT INTERFERE WITH CIRCULATOR BLOWER OPERATION FILTER REMOVAL OR ROUTINE MAINTENANCE 24 V THERMOSTAT CONNECTIONS REMOVABLE PLUG CONNECTOR IS PROVIDED WITH THE FURNACE Low Voltage Connections with Auxiliary Terminals CONTROL TO MAKE THERMOSTAT WIRE CONNECTIONS HIS PLUG MAY Figure 31 BE REMOVED...
  • Page 30: Single -Stage Heating Thermostat Application

    To enable the dehumidify function on the integrated control mod- ule, set the dehumidification ENABLE DIP switch from OFF to Furnace Integrated Once the switch is set, the dehumidify function is enabled during Control Module Field installed jumper to enable cooling a combination call for cooling (T-Stat) and dehumidification ramping profile when using a straight...
  • Page 31: Volt Humidifier

    Inlet gas supply pressures must be maintained within the ranges specified in the following table. The supply pressure must be constant and available with all other household gas fired appli- ances operating. The minimum gas supply pressure must be maintained to prevent unreliable ignition. The maximum must NEUTRAL not be exceeded to prevent unit overfiring.
  • Page 32: Gas Piping Connections

    • Use pipe joint compound on male threads ONLY. Always IPING ONNECTIONS use pipe joint compound (pipe dope) that is APPROVED FOR ALL GASES. DO NOT apply compound to the first two threads. WARNING • Use ground joint unions. O AVOID POSSIBLE UNSATISFACTORY OPERATION OF EQUIPMENT •...
  • Page 33 Gas Piping Connections Manual Shut Off Valve (upstream from ground joint pipe union) Manual Shut Off Valve Alternate Manifold Burners (upstream from Gas Line ground joint Location pipe union) Gas Valve *Ground Joint *Ground Pipe Joint Union Pipe Union Drip Leg Grommet in Standard Gas Line...
  • Page 34: Propane Gas Tanks And Piping

    A gas detecting warning system is the only reliable way to detect WARNING a propane gas leak. Rust can reduce the level of odorant in pro- pane gas. Do not rely on your sense of smell. Contact a local DGES OF SHEET METAL HOLES MAY BE SHARP SE GLOVES AS A propane gas supplier about installing a gas detecting warning PRECAUTION WHEN REMOVING HOLE PLUGS...
  • Page 35: Circulating Air & Filters

    & F Example: IRCULATING ILTERS static reading from return duct = -0.1" W.C. UCT WORK static reading from supply duct = +0.3" W.C. Duct systems and register sizes must be properly designed for the CFM and external static pressure rating of the furnace. total external static pressure on this system = 0.4"...
  • Page 36: Bottom Return Air Opening

    Consider installing an air cleaner with deep-pleated media filter at the time of furnace installation. A deep-pleated fil- WARNING ter with a MERV rating of 8 (minimum) will often provide better filtration to protect equipment and the air distribu- DGES OF SHEET METAL HOLES MAY BE SHARP SE GLOVES AS A tion system than a standard 1"...
  • Page 37: Upright Installations

    Air cleaner installation location Maximum Heating Airflow Filter (Media) Dimensions Part Number Cleaner Family Si de or bottom return 1200 CFM 16 i n X 20 i n x 5¼" AM11-1620-5 Si de or bottom return 1600 CFM 16 i n X 25 i n x 5¼" AM11-1625-5 AM11-5 Si de or bottom return...
  • Page 38: Horizontal Installations

    Call for heat, thermostat energizes W1 on the furnace FILTER control board (W2 input is ignored). ACCESS DOOR After a successful Light Off Sequence and expiration of the Ignition Stabilization Period: • The furnace control board adjusts the firing rate to 35% (low fire rate).
  • Page 39: Heating Operation With Ctk01 Thermostat

    Call for 2nd-Stage Heat satisfied; Call for 1st-Stage Heat remains. 10 MINS. • The furnace control board remains at the current 8 MINS. firing rate until the 1st-Stage call for heat is IGNITION (80%) satisfied. CTK01 T EATING PERATION WITH HERMOSTAT OMMU NICATING...
  • Page 40: Condensate Drain Trap Priming

    • If the specific heat requested demand is above 2 URNACE HUTDOWN degrees, the heat current demand status will 1. Set the thermostat to the lowest setting. track the specific heat requested demand. The integrated control will close the gas valve and •...
  • Page 41: Gas Manifold Pressure Measurement

    Figure 50A Gas Line Shutoff Valve Outlet Pressure 1/8 NPT Gas Line To Furnace Open To Atmosphere Drip Leg Cap With Fitting Manometer Hose Figure 50B Honeywell Model VR9205R Connected to Manometer Manometer 1. Turn OFF gas to furnace at the manual gas shutoff valve Measuring Inlet Gas Pressure (Alt.
  • Page 42: Gas Input Rate Measurement

    8. Field Test Mode is intended to help a service person 3. If the 1/2 cu. ft. dial was used, multiply your troubleshoot and check out an installed appliance number x 2. by bringing the furnace up to High fire (100% input), EXAMPLE: If it took 23 seconds to complete by-passing the normal modulating routing.
  • Page 43: Circulator Blower Speeds

    Example: The airflow being delivered is 1225 CFM. The display TEMPERATURE RISE indicates 12. If the airflow being delivered is 1275, the display Model HI / LO indicates 13. DM97MC0603BN** 20-50/25-55 1. Determine the tonnage of the cooling system installed with the furnace.
  • Page 44 profile. Verify CFM by noting the number displayed on High High the dual 7-segment LED display. Model Stage Stage Stage Stage • Profile A provides only an OFF delay of one (1) minute Cool Cool Heat Heat at 100% of the cooling demand airflow. 1059 DM97MC0603BN** 1007...
  • Page 45: Blower Heat Off Delay Timings

    8. Select the desired “heating” speed tap by positioning tion from both the indoor and outdoor units. This information switches 3 and 4 appropriately. Refer to the airflow may be displayed on the ComfortNet thermostat. The indoor table. Verify CFM by noting the number displayed on the and outdoor units also interact with one another.
  • Page 46: Fossil Fuel Applications

    For example, assume the system is an air conditioner matched with a furnace. With a call for low stage cooling, UTDOOR NDOOR IRING the air conditioner will calculate the system’s low stage cool- As few as two wires can be utilized between the indoor and ing airflow demand.
  • Page 47: Dip Switches

    DIP S WITCHES...
  • Page 48 CTKO* 1 & 2 CTK0* Thermostat Thermostat ComfortNet Compatible ComfortNet Compatible Furnace Furnace Integrated Integrated Control Module Control Module 40VA Transformer ComfortNet Compatible (included in CTK01 kit) AC/HP Integrated ComfortNet Compatible AC/HP Control Module Integrated Control Module 208/230 VAC 24 VAC System Wiring using Four-Wires System Wiring using Two-Wires between Furnace and AC/HP and Four-Wires between Furnace and Thermostat...
  • Page 49: System Troubleshooting

    LED Status Indication Possible Causes Corrective Action(s) Notes & Cautions •   Normal condition •   None •   None •   None 2 Flashes •   Out-of-box reset •   Control power up •   None •   None Communications •   Learn button depressed Rapid Flashing •   Normal network traffic •  ...
  • Page 50: Cooling Mode

    • • The percentage of heating demand is sent from the Furnace circulator blower and outdoor cooling unit run their furnace control board to determine what RPM the appropriate speeds, integrated control module monitors draft inducer should run at. A higher percentage safety circuits continuously.
  • Page 51: Furnace Control Board

    URNACE ONTROL OARD • R and G thermostat contacts open, completing the call for fan. The furnace control board is an electronic device which, if a • potential safety concern is detected, will take the necessary Circulator blower is de-energized. Electronic air cleaner precautions and provide diagnostic information through an terminal is de-energized.
  • Page 52: Rollout Limit

    OLLOUT IMIT IAGNOSTIC HART The rollout limit controls are mounted on the burner/manifold assembly and monitor the burner flame. They are normally- WARNING closed (electrically), manual-reset sensors. These limits guard against burner flames not being properly drawn into the heat HIGH VOLTAGE ! exchanger.
  • Page 53: Maintenance

    ILTER EMOVAL AINTENANCE Depending on the installation, differing filter arrangements can WARNING be applied. Filters can be installed in either the central return register or a side panel external filter rack (upflow only). A me- O AVOID ELECTRICAL SHOCK INJURY OR DEATH dia air filter or electronic air cleaner can be used as an alternate DISCONNECT ELECTRICAL POWER BEFORE PERFORMING ANY filter.
  • Page 54: Before Leaving An Installation

    LAME ENSOR UALIFIED ERVICER EPAIR AND EPLACEMENT ARTS • When ordering any of the listed functional parts, be Under some conditions, the fuel or air supply can create a nearly invisible coating on the flame sensor. This coating acts as an sure to provide the furnace model, manufacturing, and insulator causing a drop in the flame sense signal.
  • Page 55: Troubleshooting Codes

    ROUBLESHOOTING ODES...
  • Page 56 ROUBLESHOOTING ODES...
  • Page 57 ROUBLESHOOTING ODES...
  • Page 58 ROUBLESHOOTING ODES...
  • Page 59 ROUBLESHOOTING ODES...
  • Page 60 TATUS ODES NO POWER NORMAL OPERATION INDICATES AIRFLOW, FOLLOWED BY CFM BLOWER MOTOR NOT RUNNING BLOWER COMMUNICATION ERROR BLOWER HP MIS-MATCH BLOWER MOTOR OPERATING IN POWER, TEMPERATURE, OR SPEED LIMIT BLOWER MOTOR CURRENT TRIP OR LOST ROTOR BLOWER MOTOR LOCKED ROTOR BLOWER OVER/UNDER VOLTAGE TRIP OR OVER TEMPERATURE TRIP INCOMPLETE PARAMETERS SENT TO MOTOR LOW INDOOR AIRFLOW...
  • Page 61: Wiring Diagram

    DM97MC_A*, DC97MC_A* IRING IAGRAM DOOR SWITCH JUNCTION BOX INDUCTOR COIL (ON SOME MODELS) INDOOR CIRCULATOR BLWR LINE NEUTRAL ELECTRONIC AIR CLEANER OPTIONAL 3 ID BLWR NEUTRAL HUMIDIFIER OPTIONAL NEUTRAL HOT SURFACE IGNITER LINE NEUTRAL DIAGNOSTIC LED’S 40 VA FUSE 3A TRANSFORMER TR (5) 24 VAC...
  • Page 62: Special Instructions For Products Installed

    PECIAL NSTRUCTIONS FOR RODUCTS NSTALLED IN THE TATE OF ASSACHUSETTS For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the VENT/FLUE Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the...
  • Page 63 THIS PAGE LEFT INTENTIONALLY BLANK...
  • Page 64 NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE. Our continuing commitment to quality products may mean a change in specifications without notice. © 2014-2017 5151 San Felipe St., Suite 500, Houston, TX 77056 www.daikincomfort.com...

This manual is also suitable for:

Dm97mc

Table of Contents

Save PDF