Delta DVP EN01-SL Instruction Sheet

Ethernet communication module

Advertisement

Quick Links

http://www.delta.com.tw/industrialautomation/
Ethernet Communication Module
Instruction Sheet
Warning
This instruction sheet only provides introductory information on electrical specification, general specifications,
installation, basic operation and settings of DVPEN01-SL.. For more detailed information on the network protocols,
please refer to relevant references or literatures.
This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne dust, humidity, electric shock
risk and vibration. Also, it is equipped with protective methods such as some special tools or keys for opening the
enclosure, in order to prevent hazard to users or damage on the PLC.
Please read this instruction sheet carefully before use and follow this instruction to operate the device in order to prevent
damages on the product or injuries to staff.
Introduction
Functions:
Supports MODBUS TCP/IP
Supports E-Mail
Supports Master and Salve Data Exchange
RS-232/Ethernet Configuration
DVP28SV Automatic Time Correction
Transmission Speed: 10/100 Mbps
Nameplate Explanation
P L C M o d e l N a m e
Power Input Spec.
24Vdc 1.5W
Bar-code, Serial No.
EN 01 - S L 0T 7 0 40 00 1
Version
VX.XXXX
M A D E I N X X X X X X
Model Name and Serial Number Explanations:
EN
DVP series
Model type
Left-side module
Left-side module
Type 01
For SV series MPU
EN: Ethernet
Communication module
Outline:
1
Model name
1
DVPEN01
POWER
4
2
RS-232
Extension Port to connect Device
2
100M
LINK
3
3
Extension Port to connect Extension module
4
8
POWER, LINK, RS-232, 100M LED
5
DIN rail clip
RS-232
6
Extension hole for mounting unit or module
7
Extension clip
9
8
RS-232 port
7
6
LAN
9
Ethernet RJ-45 port
5
Product Profile: Unit mm [inchs]
3 [0.118]
DVPEN01
POWER
RS-232
100M
LINK
RS-232
LAN
2007-06-22
Specifications
Network Interface
Interface
RJ-45 with Auto MDI/MDIX
5011655400-ENE0
Number of
1 Port
ports
Transmission
IEEE 802.3, IEEE 802.3u
method
Transmission
Category 5e (TIA/EIA-568-A,TIA/EIA-568-B)
cable
Transmission
10/100 Mbps Auto-Detect
Rate
Protocol
ICMP, IP, TCP, UDP, DHCP, SMTP, NTP, MODBUS TCP
Serial Interface
Interface
RS-232
Number of
1 Port
Ports
Transmission
DVPACAB230, DVPACAB215, DVPACAB2A30, DVPACAB2B10
Cable
Environmental Specifications
Noise Immunity
Environment
Vibration/
Shock
Resistance
IP Label
MAC Address
Approvals
IP AD DR E SS
Electrical Specifications
001823100022
Power supply
SU B NE T MA SK
24VDC (-15% ~ 20%) (Power is supplied by the internal bus of MPU.)
voltage
Power
1.5W
Consumption
Insulation
500V
voltage
Weight (g)
92 (g)
Installation
Production No.
Production week
How to Connect DVPEN01-SL with PLC
Production year (2006)
1. Adjust the extension clip on the left side of the MPU.
Production plant (Taoyuan)
Version No.
2. Meet the extension port of the MPU with DVPEN01-SL and connect them as the figure shown below.
Model name
3. Fasten the extension clip.
Install DVPEN01-SL with Other Module
To connect DVPEN01-SL with the other extension module, lift the extension clip of the extension module by a
screwdriver and open the side cover.
60 [2.362]
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Operation: 0°C ~ 55°C (Temperature), 50 ~ 95% (Humidity), Pollution degree 2;
Storage: -40°C ~ 70°C (Temperature), 5 ~ 95% (Humidity)
Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
IEC 61131-2, UL508
D V P E N 0 1
D V P 28S V
PO W ER
R S -2 32
10 0M
LIN K
R S -2 32
LA N
Control Register (CR)
CR NO.
Type
Register
HW
LW
Model NO
#0
R
Read only; DVPEN01-SL model NO.=H'4050
System firmware version; The type is hex. For
#1
R
Firmware version
example, H'0100 means the firmware version is v1.00.
b0 Modbus TCP mode setting
#2
R
Communication Mode
b1 Data Exchange mode setting
#3
W
E-Mail Event 1 Trigger
Set as 1 to send the E-mail 1.
#4
W
E-Mail Event 2 Trigger
Set as 1 to send the E-mail 2.
#5
W
E-Mail Event 3 Trigger
Set as 1 to send the E-mail 3.
#6
W
E-Mail Event 4 Trigger
Set as 1 to send the E-mail 4.
#7
R
E-Mail 1, 2 Status Register
b0~b7 Status of E-Mail 2
#8
R
E-Mail 3, 4 Status Register
b0~b7 Status of E-Mail 4
#9
R/W
E-Mail 1 Additional Message
User fills the message, and it will be send by E-Mail.
#10
R/W
E-Mail 2 Additional Message
User fills the message, and it will be send by E-Mail.
#11
R/W
E-Mail 3 Additional Message
User fills the message, and it will be send by E-Mail.
#12
R/W
E-Mail 4 Additional Message
User fills the message, and it will be send by E-Mail.
#13
R/W Data Exchange trigger
Set as 1 to start the Data Exchange transaction.
#14
R
Data Exchange Status Register
Status of Data Exchange transaction
#24 ~ #15
Reserved
Reserved
#26
#25
R/W Destination IP
Destination IP address for Data Exchange
#27
Reserved
Reserved
#28
R/W Destination Slave ID
Destination Slave ID for Data Exchange
#48 ~ #29
R/W Default Transmission Buffer
Transmitted data buffer for Data Exchange mode
#68 ~ #49
R
Default Received Buffer
Received data buffer for Data Exchange mode
#69
R/W DHCP/Static IP
Select DHCP Mode or Static IP
#71
#70
R/W IP Address
IP Address
#73
#72
R/W Subnet Mask
Subnet Mask of DVPEN01-SL
#75
#74
R/W Gateway
Default gateway IP address
#76
R
Network Status Register
Status of IP address setting
#80 ~ #77
Reserved
Reserved
#81
R/W Slave Transmission Buffer Address
Slave Transmission buffer Address for Data Exchange
#82
R/W Number of Received Registers
Number of Received Registers
#83
R/W Master Received Buffer Address
Master Received Buffer Address for Data Exchange
#84
R/W Slave Received Buffer Address
Slave Received Buffer Address for Data Exchange
#85
R/W Number of Sending Registers
Number of Sending Registers
Master Transmission Buffer Address for Data
#86
R/W Master Transmission Buffer Address
Exchange
#110 ~ #87
Reserved
Reserved
#111
R/W Modbus TCP Operating Mode
Set as 1 to configure Modbus TCP be the 8 bits mode.
#113 ~ #112
Reserved
Reserved
#114 R/W Modbus TCP Time-Out
Modbus TCP transaction time-out (ms)
#115 R/W Modbus TCP Trigger
Set as 1 to send Modbus command.
#116 R/W Modbus TCP Status Register
Status of Modbus TCP transaction
The Destination IP Address of Modbus TCP
#118 ~#117 R/W Modbus TCP Destination IP
transaction
#119 R/W Modbus TCP Data Length
Data length of Modbus TCP in CR#120 ~ CR#219
Data buffer of Modbus TCP Mode for storing
#219~#120
R/W Modbus TCP Data Buffer
sending/receiving data
#250~#220
Reserved
Reserved
#251
R
Error Code
The EVPEN01-SL error code
#255~#252
Reserved
Reserved
R: Read
Symbol definition
W: Write
Basic Configuration and Status
CR#2: Communication mode setting: Set as 0 to Disable; Set as 1 to Enable.
bit #
Mode
bit # = 0
b0
Modbus TCP Mode
Modbus TCP Mode Disable
Data Exchange
b1
Data Exchange Mode Disable Data Exchange Mode Enable
Mode
CR#251: Error codes; See the table in the next page.
Description
b8~b1
Status of E-Mail 1
5
b8~b1
Status of E-Mail 3
5
bit # = 1
Modbus TCP Mode Enable

Advertisement

loading

Summary of Contents for Delta DVP EN01-SL

  • Page 1 Register Description Interface RJ-45 with Auto MDI/MDIX Model NO 5011655400-ENE0 Read only; DVPEN01-SL model NO.=H’4050 http://www.delta.com.tw/industrialautomation/ Number of 1 Port System firmware version; The type is hex. For ports Firmware version example, H’0100 means the firmware version is v1.00. Transmission IEEE 802.3, IEEE 802.3u...
  • Page 2 The content of this instruction sheet may be revised without prior notice. Please consult our distributors or For example, if the user wants to set the IP as 192.168.0.2, write H’0002 to CR#70 and H’C0A8 to CR#71. download the most updated version at http://www.delta.com.tw/industrialautomation...