Samsung AG AN4DKH Series Installation Manual page 35

Fan coil unit
Hide thumbs Also See for AG AN4DKH Series:
Table of Contents

Advertisement

(*1) Minimizing fan operation when thermostat is off:
– The fan operates for 20 seconds at an interval of 5 minutes in the Heat mode.
– When thermostat is off in the Cool mode, the fan stops or Ultra breeze function starts based on the
setting.
(*2) 1 : The fan is turned on continually when the hot water heater is turned on,
3: The fan is turned off when the hot water heater is turned on with cooling only fan coil unit.
(*3) W hen the following 2 or 3 is used as external heater On or Off signal, the signal for monitoring external
contact control will not be output.
2 : The fan is turned on continually when the external heater is turned on
3 : The fan is turned off when the external heater is turned on with cooling only fan coil unit
※ I f the fan is set to off for cooling only fan coil unit by setting the SEG9=3 or SEG15=3, you need to use an
external sensor or wired remote control sensor to detect indoor temperature exactly.
(* 4) Output occurs when operating in the Cool or Dry mode.
(* 5) An Economizer controller is required to use the Cooling output by external equipment function.
(* 6) Default setting : 5 ℃
(*7) T his function is only applicable for the 4 way cassettes. If the fan coil unit operates in the Heat mode
immediately after finishing the cooling operation, the condensated water in the drain pan becomes water
steam by the heat of the fan coil unit heat exchanger. Since the water steam might be condensed on the fan
coil unit, which may fall into a living space, use this function to remove the water steam out of the fan coil
unit by operating the fan (for maximum 20 minutes) although the fan coil unit is turned off after the Cool
mode is turned to the Heat mode.
(*8) W hen you turn off the Cool or Dry mode, the indoor unit fan automatically operates for the set time and then
stops.
(*9) Soft Off: I f no motion is detected for the Soft Off time, the MDS Kit turns off the indoor units.
Then if any motion is detected until the Hard Off time is passed, the MDS Kit restarts the indoor
units.
(*10) Hard Off: I f no motion is detected for the Hard Off time, the Mds Kit turns hard off the indoor units.
Then although any motion is detected, the MDS Kit does not restart the indoor and outdoor units.
You must manually resttart the units with the wired of wireless remote control.
Installation options for the 05 series
SEG1
0
SEG7
1
SEG13
2
Adjustable breeze
SEG19
Choose whether
3
DB68-11289A-01_IM_DVM FCU WindFree 4way_EU_EN_.indb 35
SEG2
SEG3
5
-
SEG8
SEG9
-
-
SEG14
SEG15
Water valve control
type
SEG20
SEG21
Displaying the
water-temperature
to use Interface
rise-prevention
module
error messages
SEG4
SEG5
-
-
SEG10
SEG11
-
-
SEG16
SEG17
Valve control at
Water pipe valve is
Thermo Off
installed?
SEG22
SEG23
Timing separation
of the cooling and
Forced air speed for
heating signals for
cooling / heating
the water pipe valve
SEG6
-
SEG12
-
SEG18
Control variable
when using hot
water heater or
external heater
SEG24
-
35