Relay PadPuls M1C Manual

1-channel pulse collector with case for rail mounting (reed contact or s0 interface)

Advertisement

Quick Links

1-channel pulse collector with case for rail mounting
Contents
1 Functional description...................................................................................................2
2 Installation and startup .................................................................................................3
2.1 Mounting the case..................................................................................................3
2.2 Opening the front cover..........................................................................................3
2.3 Connecting.............................................................................................................3
3 Parameterization using MBCONF ................................................................................5
3.1 Installation..............................................................................................................5
3.2 Operation ...............................................................................................................5
3.3 Sheet Info...............................................................................................................6
3.3 Sheet PadPuls M1 .................................................................................................9
4 M-Bus Telegrams .......................................................................................................12
5 Technical data ............................................................................................................14
PadPuls M1C User Manual
GmbH, Stettiner Str. 38, D-33106 Paderborn
PadPuls M1C
Art. no.: IM001GC
(Valid from M-Bus generation: $07)
(reed contact or S
interface)
0
26.09.01, Version 1.3
1

Advertisement

Table of Contents
loading

Summary of Contents for Relay PadPuls M1C

  • Page 1: Table Of Contents

    2.2 Opening the front cover..................3 2.3 Connecting......................3 3 Parameterization using MBCONF ................5 3.1 Installation......................5 3.2 Operation .......................5 3.3 Sheet Info.......................6 3.3 Sheet PadPuls M1 ....................9 4 M-Bus Telegrams .......................12 5 Technical data ......................14 PadPuls M1C User Manual 26.09.01, Version 1.3...
  • Page 2: Functional Description

    , J and other units. The configuration is very easy with the MBCONF user interface. When connected to the M-Bus the PadPuls M1C is powered from the bus. A built-in battery ensures that metering continues even if the M-Bus fails for longer than the normal calibration time for the water meter or heat counter.
  • Page 3: Installation And Startup

    Attention: Afterwards please fix the cover oriented with the notch at the top. You can use a suitable adhesive seal to prevent the housing from being opened unnoticed. 2.3 Connecting The following picture shows a typical installation including the PadPuls M1C: level converter - Bus...
  • Page 4 -“ terminals with consideration of the correct polarity. An additional power supply of 12VDC to 27VDC sourcing minimum 30mA current must be wired to the terminals “U+” and “U-“. Note: You can use only one of the two pulse inputs of PadPuls M1C. 26.09.01, Version 1.3 PadPuls M1C User Manual...
  • Page 5: Parameterization Using Mbconf

    Windows 95 / 98 / NT 4.0. The desktop PC or laptop must have a free serial RS232C interface to connect the M-Bus level converter. The PadPuls M1C to be parameterized must be connected directly (i.e. as only M-Bus device) to the M-Bus output of the level converter.
  • Page 6: Sheet Info

    This sheet shows some photos of supported M-Bus devices from the product range of the Relay GmbH, the PadMess GmbH and further manufacturer. Here are also links to the Internet page, from which the current version of the program can be downloaded, and to the email address for criticism and suggestions to the program.
  • Page 7 The items “Manufact.”, “Generation”, “Type” and “M-Bus State” will then be refreshed. New sheets are generated depending on manufacturer and type of the M-Bus device. In case of PadPuls M1C a sheet labelled with “PadPuls M1” appears. Manufact.
  • Page 8 The following buttons are also always visible: Erase log clears all outputs inside the log window. Exit terminates the program and stores the current setting of serial port (port no.) into the INI file. 26.09.01, Version 1.3 PadPuls M1C User Manual...
  • Page 9: Sheet Padpuls M1

    GmbH, Stettiner Str. 38, D-33106 Paderborn 3.3 Sheet PadPuls M1 These sheet shows the actual settings and values of the PadPuls M1C. The following input boxes and buttons are used to change the params of the pulse adapter: Primary address is the M-Bus address of the device.
  • Page 10 “Unprotect” pushbutton. Permanent error is insignificant for the PadPuls M1C. Write protect Transmits a command to the PadPuls M1C to activate write protection. The PadPuls then allows no further configuration. It is protected against unnoticed manipulation. Read reads the M-Bus device and refreshes the data on the selected sheet.
  • Page 11 Choice: Unit = 1kWh, Multiplicator = 1 / 64, Counter = 78346 ( x 1kWh) • Electricity meter with counter = 112,345 kWh and 1000 pulses / kWh: Choice: Unit = 1Wh, Multiplicator = 1 / 1, Counter = 1123454 ( x 0,001Wh) PadPuls M1C User Manual 26.09.01, Version 1.3...
  • Page 12: Bus Telegrams

    • VIF: Set by the user; VIF = unit with decimal power (MSB not set) • Count: Meter reading (most-significant byte = Count6 always zero) • Numerator / Denominator: Impulse value (increment in multiples of the VIF per impulse): Numerator • VIF 1 Pulse = Denominator 26.09.01, Version 1.3 PadPuls M1C User Manual...
  • Page 13 4) Telegram to Set the Write Protection Byte Name Start Length Length Start Spez. Protect Stop Inhalt The write protection can only be reset by pressing the pushbutton on the circuit board. PadPuls M1C User Manual 26.09.01, Version 1.3...
  • Page 14: Technical Data

    1.2ms Connection cable Maximum 2 m twisted pair with shielding connected only on the PadPuls side -Interface Supply voltage 12VDC to 27VDC, minimum 30mA Detecting level Current limit 20mA Guaranteed debouncing time 0.25ms 26.09.01, Version 1.3 PadPuls M1C User Manual...
  • Page 15 M-Bus: physical characteristics M-Bus quiescent current typ. 1.25 mA, max. 1.5mA (1 unit load) Space (0-bit) current quiescent current + typ. 14 mA M-Bus interface TI TSS721 with 2 x 215Ω protection resistors PadPuls M1C User Manual 26.09.01, Version 1.3...
  • Page 16 GmbH, Stettiner Str. 38, D-33106 Paderborn Notes: 26.09.01, Version 1.3 PadPuls M1C User Manual...