Siemens simovert EMC-Filter Compact PLUS Operating Instructions Manual page 47

Table of Contents

Advertisement

Available languages

Available languages

09.99
X1 input
X2 output
NOTE
Siemens AG
6SE7087-7NP87-0FB0
SIMOVERT MASTERDRIVES
The terminal is on the bottom of the unit. It is for connecting the radio-
interference filter to the power supply voltage.
Terminal
Significance
PE
Protective conductor terminal
L3
Phase L3
L2
Phase L2
L1
Phase L1
Connectable cross-section: 4 mm² (AWG 10)
Terminal PE is at the front when unit has been installed.
Table 5-1
Terminal X1: input of the radio-interference filter
The terminal is on the top of the unit. It is for connecting the radio-
interference filter to the connected converter.
Terminal
Significance
L1'
L2'
L3'
PE
Protective conductor terminal
Connectable cross-section: 4 mm² (AWG 10)
Terminal PE is at the front when unit has been installed.
Table 5-2
Terminal X2: output of the radio-interference suppression filter
Please ensure that the cable from the supply system to the filter input
and the output cables of the converter are laid separately from each
other.
Operating Instructions
3AC 380 V - 480 V
3AC 380 V - 480 V
3AC 380 V - 480 V
3AC 380 V - 480 V
Phase L1'
3AC 380 V - 480 V
Phase L2'
3AC 380 V - 480 V
Phase L3'
3AC 380 V - 480 V
3AC 380 V - 480 V
Connecting-up
Range
Range
5-3