3. Click Calibrate.
4. If the A/D count is 100 +/- 30 (70 to 130), click Calibrate.
5. If the A/D count is less than 70 or greater than 130:
a. Check for blocked air hoses or wind interference.
b. Open the Trio. On the Main Board, find the Static Pressure Sensor.