Drain Piping - Toshiba MMU-UP YHP-E Series Installation Manual

Multi type air conditioner, indoor unit, 1-way cassette type
Table of Contents

Advertisement

„ Installation of ceiling panel
(Sold separately)
Install the ceiling panel according to Installation
Manual attached with it after piping / wiring work has
completed.
Check that installation of indoor unit and ceiling
opening part is correct, and then install it.
REQUIREMENT
y Joint the connecting sections of ceiling panel,
ceiling surface, ceiling panel and indoor unit
closely.
Any gap between them will cause air leakage
and the generate condensation or water leakage.
y Remove the adjust corner caps at the four
corners of the ceiling panel, and then install the
ceiling panel onto the indoor unit.
y Make sure that the claws of the four adjust
corner caps are securely fit.
* Improper fitting of the claws may cause water
leakage.
„ Installation of remote
controller (Sold separately)
For installation of the wired remote controller, follow
the Installation Manual attached with the remote
controller.
y Pull out the remote controller cord together with the
refrigerant pipe or drain pipe.
Be sure to pass the remote controller cord through
upper side of the refrigerant pipe and drain pipe.
y Do not leave the remote controller at a place
exposed to the direct sunlight and near a stove.
21-EN
„ Wireless type
(Sold separately)
The sensor of indoor unit with wireless remote
controller can receive a signal by distance within
approx. 7 m. Based upon it, determine a place where
the remote controller is operated and the installation
place.
y Operate the remote controller, confirm that the indoor
unit receives a signal surely, and then install it.
y Keep 1 m or more from the devices such as
television, stereo, etc.
(Disturbance of image or noise may generate.)
y To prevent a malfunction, select a place where is not
influenced by a fluorescent light or direct sunlight.
y Two or more (Up to 6 units) indoor units with wireless
type remote controller can be installed in the same
room.
Signal receiving unit
7 m
– 11 –
5

Drain piping

CAUTION
Following the Installation Manual, perform the
drain piping work so that water is properly
drained, and apply a heat insulation so as not to
cause a dew dropping.
Inappropriate piping work may result in water
leakage in the room and wet of furniture.
„ Piping / Heat insulating
material
Require the following materials for piping and heat
insulating at site.
Hard vinyl chloride pipe VP25
Piping
(Outer dia. : Ø32 mm)
Foam polyethylene :
Heat insulator
Thickness 10 mm or more
„ Flexible hose
Use the attached flexible hose to adjust centre
discrepancy of the hard vinyl chloride pipe or to adjust
the angle.
y Do not use the flexible hose as stretched, or do not
deform it more extent than that in the following figure.
y Be sure to fix the soft end of the flexible hose with
the attached hose band.
y Use the flexible hose on a horizontal level.
OK
NO GOOD
max
45°
max
45°
REQUIREMENT
y Be sure to perform heat insulation of the drain
pipes of the indoor unit.
y Never forget to perform heat insulation of the
connecting part with the indoor unit.
An incomplete heat insulation causes dew
dropping.
y Set the drain pipe with downward slope (1/100 or
more), and do not make swelling or trap on the
piping.
It may cause an abnormal sound.
1.5 m to 2 m
1/100 or more
Heat insulator
downward
y For length of the traversing drain pipe, restrict to
20 m or less.
In case of a long pipe, provide support brackets
with interval of 1.5 to 2 m in order to prevent
waving.
Arched
shape
Trap
y Set the collective piping as shown in the below
figure.
As long as possible (10 cm)
VP25
VP25
VP30 or more
y Be sure not to apply force to the connecting part of
the drain pipe.
y The hard vinyl-chloride pipe cannot be directly
connected to the drain pipe connecting port of the
indoor unit.
For connection with the drain pipe connecting port,
be sure to use / fix the attached flexible hose with
the hose band, otherwise a damage or water leak
is caused on the drain pipe connecting port.
Attached hose
Drain pipe
band
connecting port
(Hard socket)
Attached flexible hose
Riser (Trap)
Soft socket
90° Bend
Hard socket
Adhesive inhibited :
Use the attached flexible hose and hose band for
connecting the drain hose to the clear drain socket.
If applying the adhesive, socket will be damaged and
cause water leakage.
5 mm or less
Drain pipe
connecting port
(Transparent)
10 mm
Support
bracket
Flexible hose
Heat
(Accessory)
insulator
NO
GOOD
VP25
Downward slope
1/100 or more
VP25 vinyl chloride pipe
(Locally procured)
Socket for VP25
(Locally procured)
10 to 12 mm
hose band tightening
margin
VP25 vinyl chloride
pipe
(Locally procured)
Socket for VP25 vinyl
chloride pipe
(Locally procured)