Toshiba MMU-UP YHP-E Series Installation Manual page 19

Multi type air conditioner, indoor unit, 1-way cassette type
Table of Contents

Advertisement

8
Applicable controls
REQUIREMENT
When the air conditioner is used for the first time,
it will take some moments after the power has
been turned on before the remote controller
becomes available for operations: This is normal
and is not indicative of trouble.
y Concerning the automatic addresses
(The automatic addresses are set up by
performing operations on the outdoor interface
circuit board.)
While the automatic addresses are being set
up, no remote controller operations can be
performed. Setup takes up to 10 minutes (usually
about 5 minutes).
y When the power is turned on after automatically
address setup, It takes up to 10 minutes (usually
about 3 minute) for the outdoor unit to start
operating after the power has been turned on.
Before the air conditioner was shipped from the
factory, all units are set to [STANDARD] (factory
default).
If necessary, change the indoor unit settings.
The settings are changed by operating the wired
remote controller.
* The settings cannot be changed using only a
wireless remote controller and simple remote
controller by itself so install a wired remote
controller separately as well.
„ Applicable controls setup
(settings at the site)
Remote controller model name:
RBC-ASCU11-E
Basic procedure
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not
working.)
CAUTION
Set only the Code No. shown in the following table:
Do NOT set any other Code No.
If a Code No. not listed is set, it may not be possible
to operate the air conditioner or other trouble with
the product may result.
35-EN
1
Push and hold menu button and [
]
setting button simultaneously for
10 seconds or more.
y After a while, the display flashes as shown in the
figure. "ALL" is displayed as indoor unit numbers
during initial communication immediately after
the power has been turned on.
Indoor unit No.
2
Each time [
] [
] setting button is
pushed, indoor unit numbers in the group
control change cyclically. Select the indoor
unit to change settings for.
y The fan of the selected indoor unit runs.
The indoor unit can be confirmed for which to
change settings.
3
Push OFF timer button to confirm the
selected indoor unit.
Code No.
Set data
4
Push the menu button to make Code No.
[
] flash. Change Code No. [
] with
[
] [
] setting button.
5
Push the menu button to make Set data
[
] flash. Change Set data [
with [
] [
] setting button.
6
Push OFF timer button.
By doing so, the setup is completed.
y To change other settings of the selected indoor
4
unit, repeat from Procedure
.
7
When all the settings have been completed,
push ON/OFF button to determine the
settings.
"
" flashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while "
" is flashing.)
y To change settings of another indoor unit, repeat
1
from Procedure
.
– 18 –
„ Installing indoor unit on high
ceiling
]
When an indoor unit is installed on a ceiling higher
than the standard height, make the high-ceiling setting
for fan speed adjustment.
Follow to the basic operation procedure
1
2
3
4
5
6
(
).
4
y For the CODE No. in Procedure
, specify [5d].
5
y Select the SET DATA for Procedure
from the
"Height list of ceiling possible to be installed" table in
this manual.
‹ Remote controller-less setting
Change the high-ceiling setting with the DIP switch on
the receiver section P.C. Board.
For details, refer to the manual of the wireless remote
controller kit. The settings can also be changed with
the switch on the indoor microcomputer P.C. Board.
* Once the setting is changed, setting to 0001 is
possible, however setting to 0000 requires a
setting data change to 0000 using the wired remote
controller (separately sold) with the normal switch
setting (factory default).
1
O
N
2
MCU(IC501)
SW501-1
1
O
N
2
SW501-2
SET DATA
SW501-1
0000
OFF
(Factory default)
0001
ON
To restore the factory defaults
To return the DIP switch settings to the factory
defaults, set SW501-1 and SW501-2 to OFF, connect
a separately sold wired remote controller, and then set
the data of CODE No. [5d] to "0000".
SW501-2
OFF
OFF
36-EN